2020-07-27 10:27:211) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1.
 2) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON
 THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SIZE ALL THE INDIVIDUAL BRANCH LINES TO THE
 APPLIANCES/EQUIPMENT.
 4) SHOW THE REQUIRED SHUTOFF VALVES FFOR EACH
 APPLIANCE. FBC-FUEL GAS SEC.409.5.
 5) A UNION IS REQUIRED WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF THE REGULATOR AT THE OUTLET OF THE GAS
 METER. FBC-GAS SEC.410.2 (7).
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. FBC-FUEL GAS SEC.304.1.
 7) UPON ACTIVATION OF ANY FIRE-EXTINGUISHING SYSTEM FOR
 A COOKING OPERATION, ALL SOURCES OF FUEL AND ELECTRICAL
 POWER THAT PRODUCE HEAT TO ALL EQUIPMENT REQUIRING
 PROTECTION BY THAT SYSTEM SHALL AUTOMATICALLY SHUT OFF
 PER 2014 NFPA 96, SEC. 10.4.1.
 8) A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN.
 AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT
 OF A FIRE, BE LOCATED IN A PATH OF EGRESS, AND CLEARLY
 IDENTIFY THE HAZARD PROTECTED. NFPA 96, SEC. 10.5.1.
 9) AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M
 (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S)
 WITHIN A PATH OF EGRESS OR AT AN ALTERNATIVE LOCATION
 ACCEPTABLE TO THE AHJ.
 10) THE SHUTOFF VALVE FOR THE APPLIANCE SHALL BE
 LOCATED IN THE SAME ROOM AND WITHIN 6 FEET OF THE
 APPLIANCE. FBC-FUEL GAS SEC.409.5.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  