Plan Review Notes For Permit 20070268 |
Permit Number |
20070268 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-30 15:27:52 | SIGN | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW ALL ATTACHMENT (WELDS, BOLTS, SCREWS | | ETC.) SIZES, TYPE AND ON CENTER SPACING TO FABRICATE | | THE SIGN AND GRAPHICS. | | 2) SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC OR | | DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP | | BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS | | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE | | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN | | REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING | | [email protected] AND ASKING FOR THE FORM | | |
|