2020-10-06 11:20:26 | PLAN REVIEW GENERATOR - BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE SITE SPECIFIC DESIGN WIND LOADS. WIND LOADS |
| SHALL BE BASED ON VULT OF 170MPH/VASD OF 132MPH. |
| INCLUDE RISK AND EXPOSURE CATEGORIES. PROVIDE MEAN ROOF |
| HEIGHT OF STRUCTURE. |
| |
| 2. PROVIDE DESIGN WIND LOADS OF GENERATOR. |
| |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). |
| |
| NOTE: SITE CAST GENERATOR PAD APPROVED. |
| |
| |
| 1ST REVIEW COMMENTS |
| |
| PRE-FAB GENERATOR PAD |
| |
| 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC |
| 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD |
| ENGINEERING. |
| 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE |
| SIGNED AND SEALED BY A DESIGN PROFESSIONAL. |
| 3) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD. |
| 4) PROVIDE A SITE PLAN. SHOW LOCATION OF PROPOSED |
| GENERATOR. |
| |