Plan Review Notes
Plan Review Notes For Permit 20070245
Permit Number 20070245
Review Stop B
Sequence Number 2
Notes
Date Text
2020-10-06 11:20:26PLAN REVIEW GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE SPECIFIC DESIGN WIND LOADS. WIND LOADS
 SHALL BE BASED ON VULT OF 170MPH/VASD OF 132MPH.
 INCLUDE RISK AND EXPOSURE CATEGORIES. PROVIDE MEAN ROOF
 HEIGHT OF STRUCTURE.
  
 2. PROVIDE DESIGN WIND LOADS OF GENERATOR.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 NOTE: SITE CAST GENERATOR PAD APPROVED.
  
  
 1ST REVIEW COMMENTS
  
 PRE-FAB GENERATOR PAD
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
 3) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
 4) PROVIDE A SITE PLAN. SHOW LOCATION OF PROPOSED
 GENERATOR.
  