2020-09-15 08:47:52 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT-20070232 |
| 9/15/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COMMENTS #3 & 5 FROM THE 1ST REVIEW PRINTED BELOW WERE |
| NOT ADDRESSED. PLEASE COMPLY WITH THE COMMENTS. THE |
| REQUESTED RESPONSE NARRATIVE WAS ALSO NOT PROVIDED. |
| |
| 3) BATH TUB/SHOWER CONVERSION: SHOW THE LOCATION OF THE |
| NEW DRAIN IN THE DRAWING AND INDICATE IF IT BEING |
| RELOCATED OR REUSED IN THE ORIGINAL TUB/SHOWER |
| LOCATION. A DETAIL IS REQUIRED FOR A RELOCATED DRAIN |
| BASED ON SECTION 1002.1: THE VERTICAL DISTANCE FROM THE |
| FIXTURE OUTLET TO THE TRAP WEIR SHALL NOT EXCEED 24 |
| INCHES, AND THE HORIZONTAL DISTANCE SHALL NOT EXCEED 30 |
| INCHES MEASURED FROM THE CENTERLINE OF THE FIXTURE |
| OUTLET TO THE CENTERLINE OF THE INLET OF THE TRAP. |
| |
| 5) FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE THE |
| BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE |
| ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND |
| THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING |
| UNITS, THE ALTERATIONS THAT ARE PROPOSED IN THE |
| BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR |
| HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES |
| ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017 |
| SIXTH EDITION. REFER TO REQUIRMENT 7 USUABLE KITCHENS |
| AND BATHROOMS AND PAGE 7.33 IN THE FAIR HOUSING ACT |
| DESIGN MANUAL. |
| BASED ON THE DRAWING IT IS NOT CLEAR IF USABLE BATHROOM |
| TYPE A OR B WAS CHOSEN AS THE ORIGINAL DESIGN UNDER |
| PERMIT-01091471, HOWEVER THE DRAWING APPEARS TO |
| INDICATE THAT THE MASTER BATHROOM WAS DESIGNED AS A |
| TYPE B BECAUSE GREATER ACCESS IS PROVIDED TO THE |
| TUB/SHOWER UNIT. BECAUSE IT IS THIS TUB/SHOWER UNIT |
| BEING CONVERTED TO A SHOWER, THE REQUIRED CLEAR FLOOR |
| 30?X 48? CLEAR FLOOR SPACE FOR WHEELCHAIR APPROACH MUST |
| BE MAINTAINED. AS REQUESTED IN COMMENT #1 PROVIDE AN |
| ENLARGED DRAWING OF THE SHOWER THAT INCLUDES THE |
| DIMENSIONS OF THE SHOWER AND THE REQUIRED CLEAR FLOOR |
| SPACE DIAGRAM AND DIMENSION- REFER TO SEE REQUIRMENT 7 |
| AND FIGURE 7D FOR GUIDANCE. COMPLIANCE ALSO REQUIRES |
| THAT BACKING FOR FUTURE GRAB BAR INSTALLATIONS BE |
| PROVIDED ? REFER TO FIGURE 5 AND PROVIDE DIMENSIONED |
| SIDE AND BACK ELEVATION VIEWS OF THE SHOWER WALLS |
| SHOWING THE LOCATIONS, LENGTHS AND WIDTHS OF THE GRAB |
| BAR BACKINGS. |
| |
| PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| SO REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| COPY OF THE FAIR HOUSING AFFIDAVIT. IF CHOOSING THIS |
| OPTION IT WOULD BE ADVISABLE AT A MINIMUM TO INSTALL |
| THE SHOWER WALL REINFORCEMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |