2020-09-21 11:17:34 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20070232 |
| ADD: 616 CLEARWATER PARK DR # 312 |
| CONT: TRYMACK DEVELOPERS |
| TEL: 561-632-8396 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE:MON. SEPT.21ST/2020 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST,THE DESIGNER OF RECORD QOUTED THE CODE |
| SECTION THAT NEED TO SHOW COMPLIANCE. PLEASE REVIEW THE |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1. |
| W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES " THE CODE SHALL NOT BE CITED AS A |
| WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1ST ROUND OF COMMENTS. BATH # 2 SHOWS THE CHANGING OF A |
| TUB TO A SHOWER, IT IS ASSUMED THAT WHATEVER BACKER |
| BOARD IS THERE NOW PROBABLY WATER RESISTANT DRYWALL |
| (GREENBOARD) IS BEING REMOVED. THE PLANS DO NOT STATE |
| WHAT TYPE OF BACKER BOARD IS GOING BACK IN ITS PLACE. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION: |
| 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A |
| BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| THE MANUFACTURE?S RECOMMENDATIONS. |
| |
| |
| 2) THE ORIGINAL PLANS NOR PERMIT APPLICATION INDICATED |
| THE REMOVAL AND REPLACEMENT OF FLOOR COVERINGS, |
| FLOOR INSULATION (FBC-B 2017) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING |
| COMPLIANCE WITH: |
| |
| TYPE I AND II BUILDINGS |
| 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |