Plan Review Notes For Permit 20070229 |
Permit Number |
20070229 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-15 09:03:18 | WINDOWS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) BUILDING APPEARS TO BE A 4 STORY CONDO BUILDING - | | PLEASE SHOW THE CORRECT MEAN ROOF HEIGHT. | | 2) PLEASE PROVIDE SIGNED AND SEALED WIND DESIGN | | PRESSURES FROM AN ARCHITECT OR ENGINEER SHOWING THE | | WIND DESIGN CRITERIA FBC 1609 | | 3) PLEASE SHOW ON A FLOOR PLAN THE LOCATION OF THE UNIT | | WITHIN THE BUILDING FOOT PRINT- REQUIRED TO DETERMINE | | IF IN WIND ZONE 4 OR 5 | | 4) IF THIS IS AN END UNIT PLEASE SHOW THE DISTANCE FROM | | THE CORNER OF THE BUILDING TO THE EDGE OF THE WINDOWS | | ON THE CORNERS OF THE BUILDING - REQUIRED TO DETERMINE | | IF IN WIND ZONE 4 OR 5. | | |
|