2020-07-13 14:49:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS AN INDICATON ON THE RESPONSE SHEET # 5 |
| REGARDING DOCUMENTS FROM THE EOR. |
| |
| THE APPROVAL OF THIS REVISION WILL BE PENDING THE |
| DOCUMENTS AND THE REVISED DRAWINGS OF THE MASTER PLAN |
| SHEETS SPECIFICALY TO THE REQUIRED SEPARATION AND |
| PENETRATION POINTS. |
| |
| |
| |
| 2) THERE IS AN INDICATON ON THE RESPONSE SHEET # 4 |
| REGARDING THE PIPING REMOVAL. |
| |
| THE PREVIOUS APPROVAL OF PERMIT #19120231 HAD HYDRAULIC |
| CALCULATIONS FOR REMOTE AREA # 4. |
| |
| THE PROPOSED REMOVAL OF THIS PIPING AND ANY RELATED |
| RECORD SHALL ALOS REQUIRE A REVISION OF THE PREVIOUSLY |
| APPROVED HYDRALIC CALCULATIONS. |
| |
| PLEASE PROVIDE AN OFFICIAL RETRACTION OF THOSE |
| CALCULATIONS. |
| |
| |
| |
| 3) WITH THE ADDITION OF THE CORRIDOR SPRINKLERS, IT |
| PPEARS THAT THE POTENTIAL FOR THE PREVIOUSLY APPROVED |
| REMOTE AREAS # 1 THRU 3 MAY BE AFFECTED. |
| |
| PLEASE PROIVDE A REVIEW OF THOSE AREAS AND CORRECT OR |
| PROVIDE A DETAILED NARRATIVE THAT THOSE AREAS ARE NOT |
| AFFECTED NOR CHANGED. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |