Plan Review Notes For Permit 20070137 |
Permit Number |
20070137 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2020-09-02 11:12:16 | WINDOWS/DOOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PRODUCT APPROVAL FL16893 R2 HAS EXPIRED IT HAS BEEN | | REPLACED BY FL16893 R5 (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) - PLEASE PROVIDE AN UPDATED | | PRODUCT APPROVAL FOR THE SHUTTERS. | | 2) WEST PALM BEACH REQUIRES THAT A "SCHEDULE FOR | | INSTALLATION OF OPENING PROTECTIVE DEVICES OR | | ASSEMBLIES" NEEDS TO BE FILLED OUT FOR SHUTTER | | INSTALLATION OR PROVIDE ALL INFORMATION REQUIRED IN | | ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET) | | WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE NOTE | | FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE DISTANCE AND | | FASTENER. FOR FASTENER, IF USING TAPCON, BE SPECIFIC AS | | TO WHICH TAPCON (TAPCON W/ADVANCED THREADFORM | | TECHNOLOGY REQUIRES A .9 FACTOR). | | FORMS CAN BE PROVIDED BY EMAILING [email protected] AND ASKING | | FOR "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE | | DEVICES OR ASSEMBLIES? FORM. | | OR SEND ME AN EMAIL AND I CAN SEND YOU THE FORM | | ([email protected]) | | | | |
|