Plan Review Notes For Permit 20070111 |
Permit Number |
20070111 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-08-15 13:48:29 | PLAN REVIEW GENERATOR FUEL GAS | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 3RD REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. GAS RISER DIAGRAHM IS MISSING FROM SUBMITTAL. FILE | | LABLED GAS RISER IS THE NEW ELECTRIC RISER. | | | | NOTE: SEND THE GAS RISER TO MY E-MAIL. I'LL MAKE SURE | | IT GETS UPLOADED TO YOUR FOLDER IN PROJECT DOX. I'LL | | HAVE TO STAMP THE NEW GAS RISER PLAN SHEET. I'LL SIGN | | OFF ON THE GAS REVIEW AND LET THE PERMIT LIBRARIANS | | KNOW YOUR REVIEWS ARE COMPLETE. | | | | |
|