2020-07-28 09:44:42PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) ELECTRICAL RISER
 PROVIDE CONDUCTOR SIZE AND TYPE OF CONTROL CIRCUIT
 WIRING. 215.5; WPB FBC 107.2.1
  
  
 3) PROVIDE DETAIL OF GROUNDING ELECTRODE SYSTEM AT
 SERVICE
 PROVIDE DETAILS OF GROUNDING ELECTRODE SYSTEM AT
 SERVICE TO RISER DIAGRAM. NEC 250.32; FBC RE3607.3
  
  
  