Plan Review Notes
Plan Review Notes For Permit 20070093
Permit Number 20070093
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-10 12:42:28SHUTTER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE BUILDING EGRESS - WHEN SHUTTERS ARE
 INSTALLED --- FBC R310.4 WHILE SUCH PROTECTION IS
 PROVIDED, AT LEAST ONE MEANS OF ESCAPE FROM THE
 DWELLING OR DWELLING UNIT SHALL BE PROVIDED. THE MEANS
 OF ESCAPE SHALL BE WITHIN THE FIRST FLOOR OF THE
 DWELLING OR DWELLING UNIT AND SHALL NOT BE LOCATED
 WITHIN A GARAGE WITHOUT A SIDE-HINGED DOOR LEADING
 DIRECTLY TO THE EXTERIOR. OCCUPANTS IN ANY PART OF THE
 DWELLING OR DWELLING UNIT SHALL BE ABLE TO ACCESS THE
 MEANS OF ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR
 NOT UNDER THEIR CONTROL.
 2) COMPLETE THE FORM TITLED "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES OR ASSEMBLIES" OR PROVIDE
 ALL INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS
 EXCEL SPREADSHEET). WHEN COMPLETING THE INSTALLATION
 SCHEDULE, PLEASE NOTE FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY MAY REQUIRE A .9
 FACTOR).
  
 FORMS CAN BE PROVIDED BY EMAILING [email protected] AND ASKING
 FOR "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES? FORM.
  
  