Plan Review Notes
Plan Review Notes For Permit 20070078
Permit Number 20070078
Review Stop G
Sequence Number 2
Notes
Date Text
2020-09-01 17:23:4908/31/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A GAS/LP PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK OR PUT A NOT ON PLANS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. PLEASE LABEL THE METER TO REFLECT 2 PSI SYSTEM AND
 ON THE GAS SYSTEM CHARTS REMOVE (DROP) NEXT TO
 PRESSURE, ADD PSI TO THE FIRST BOX AND FOURTH PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, PE
 AND OR METAL ON ISOMETRIC PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION FOR RANGE AIR PER
 THE 2017 FBC FG SEC. 304.1, 614.5.
  
 6. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (GENERATOR, RANGE, POOL HEATER, TANKLESS AND DUAL FUEL
 CHANGEOVER) TO VERIFY COMPLIANCE WITH 2017 FBC FG
 SEC.305.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC FG SECS. 402.2 AND 301.3.
  
 8. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2.
  
 9. PLEASE LABEL ALL SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 10. PLEASE LABEL ALL DRIP LEG ON EQUIPMENT INSTALLED ON
 ISOMETRIC PER THE 2017 FBC RES. SEC. G2419.2.
  
 11. FOR THE DEVELOPED LENGTH ON PIPES I HAVE 363' AND
 YOU HAVE 398' PLEASE RECALCULATE AND CHANGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 12. PLEASE LABEL GAS CHARTS AND LP CHARTS DIFFERENTLY
 AS THEY ARE TWO SEPARATE SYSTEMS PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 13. I AM COMING UP WITH 2,957 BTU'S ON GAS SYSTEM AS
 YOU CAME UP WITH 2,449 BTU'S AND LP HAS 1,305 BTU'S,
 THE GENERATOR MUST BE AT FULL LOAD PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 14. PROVIDE ON A HOUSE THE LOCATION OF THE TANKLESS
 WATER HEATER THE LOCATION AND DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 15. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2.
  
 16. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE
 TO COMPLY WITH NFPA 58 SEC. 6.6.6.1.
  
 17. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION PER THE NFPA 58 SEC.
 6.6.1.6.
  
 18. ON THE LP TANK TIE-DOWN ARE YOU USING STRAPS OR
 CABLE, IF CABLE, HOW IS IT PROTECTED FOR THE LP TANK
 AND APPURTENANCES PER NFPA 58 AND PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 10. A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER THE NFPA 58 SEC.6.6.6.1 (J). SUBMIT
 DETAILS ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.)
 & A NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE
 CABLE AMOUNT OF WATER TO ACTIVATE IT WITH THE PROCIDURE
 TO DO SO.
  
 20. THE SUBMITTED SHEET FOR THE LOCATION OF THE
 UNDERGROUND LP TANK INSTALLATION IS FOR ILLUSTRATIVE
 PURPOSES ONLY. THE LOCATION OF THE UNDERGROUND LP TANK
 SHALL COMPLY WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE
 DISTANCE OF THE LP TANK FROM THE EXTERIOR WALL OF THE
 STRUCTURE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  