2020-07-30 18:09:48 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| PERMIT- 20070078 |
| 7/29/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE SANITARY ISOMETRIC AND WATER RISER DRAWINGS- |
| SECTIONS 107.3.5.3 AND 107.2.1 WPB. PLEASE NOTE THE |
| WATER RISER SHALL SHOW PIPE SIZES, AND THE LOCATIONS OF |
| ALL SHUTOFF VALVES AND DEVICES SUCH AS WATER HAMMER |
| ARRESTORS AND BACKFLOW PREVENTERS WHERE REQUIRED- REFER |
| TO SECTIONS P2902.3 AND P2903.5 FBC RES. THE SANITARY |
| RISER SHALL SHOW DWV PIPE SIZES AND LOCATIONS OF |
| REQUIRED CLEANOUTS. |
| |
| 2) SEPARATE PERMITS ARE REQUIRED FOR THE WATER SERVICE |
| BACKFLOW PREVENTER, NATURAL GAS PIPING INSTALLATIONS, |
| THE BACKUP UNDERGROUND LP GAS TANK, AND THE IRRIGATION |
| SYSTEM. PLEASE PLACE NOTES ON THE PLAN TO CLARIFY THE |
| SCOPE OF WORK UNDER THIS PERMIT- SECTION 107.2.1 WPB. |
| |
| 3) SHEET C-101: PLEASE NOTE UPON COMPLETION OF THE NEW |
| STORM DRAINAGE SYSTEMS AS SHOWN ON THE PLAN A |
| CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE FINAL |
| APPROVAL- SECTION 110.9 IMPACT OF CONSTRUCTION WPB. IN |
| ACCORDANCE WITH NOTE 1 ON SHEET C-100, A COMPLETE SET |
| OF SIGNED AND SEALED AS-BUILT DRAWINGS SHALL BE |
| SUBMITTED BY THE FL. LICENSED SURVEYOR. |
| |
| 4) THE ROOF DRAINAGE SYSTEMS SHALL BE IN COMPLIANCE |
| WITH SECTIONS R903.4.1 FBC RES AND 1101.2 FBC P: |
| A) VERIFY THE ROOF IS DESIGNED FOR THE MAXIMUM POSSIBLE |
| DEPTH OF WATER THAT WILL POND THEREON AS DETERMINED BY |
| THE RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS, |
| SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION |
| WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING |
| THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF |
| DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED- SECTION |
| 1101.7. |
| B) PROVIDE THE ROOF DRAIN FLOW RATE BASED ON SECTION |
| 1105.2, AND CALCULATIONS FOR SIZING THE PRIMARY AND |
| EMERGENCY VERTICAL CONDUCTORS AND LEADERS AND |
| HORIZONTAL BRANCHES BASED ON SECTIONS 1106.1, FIGURE |
| 1106.1 AND SECTION 1108.3. PROVIDE A STORM DRAIN PIPE |
| SIZING SCHEDULE BASED ON TABLE 1106.2, AND VERTICAL |
| LEADER AND HORIZONTAL GUTTER SCHEDULES BASED ON TABLES |
| 1106.3 AND 1106.6. |
| C) PROVIDE A ROOF DRAIN SCHEDULE ON THE PLAN SHOWING |
| THE MAKES AND MODELS OF THE PRIMARY AND EMERGENCY ROOF |
| DRAINS, AND SUBMIT PRODUCT SPECIFICATION SHEETS- |
| SECTIONS 1102.6 AND 1108.1. |
| D) SHOW THE REQUIRED CLEANOUT LOCATIONS ON THE PLUMBING |
| PLANS FOR THE SYSTEM. PLEASE NOTE THAT CLEANOUTS ARE |
| REQUIRED WHERE THE VERTICAL CONDUCTORS CONNECT WITH THE |
| HORIZONTAL BRANCHES, AND ACCESS TO THOSE CLEANOUTS |
| SHALL BE PROVIDED- SEE SECTIONS 1101.8, 708.1.4, |
| 708.1.10 FBC P AND P3005.2.4, AND P3005.2.10 FBC RES. |
| E) PROVIDE A RISER DRAWING FOR THE ROOF DRAINAGE |
| SYSTEM- SECTION 107.3.5.3 FBC RES. |
| F) PROVIDE A ROOF DRAINAGE TESTING PROCEDURE ON THE |
| PLANS PER SECTION 1101.4 FBC P. |
| |
| 5) SHEET P-100: AS NOTED IN COMMENT #2 THE UG LP TANK |
| SHALL BE UNDER SEPARATE PERMIT. PLEASE NOTE THAT THE |
| TANK SHALL BE ANCHORED AGAINST FLOTATION- SECTION |
| 6.8.1.6 NFPA 58. AND VEHICULAR BARRIER PROTECTION SHALL |
| BE PROVIDED FOR CONTAINER'S FITTING HOUSING, HOUSING |
| COVER, CONTAINER CONNECTIONS, AND PIPING- SECTION |
| 6.8.6.1- NFPA 58. |
| |
| 6) P-100: THE 1-1/2 WATER SERVICE LINE BY THE SOUTH |
| GARAGE IS MISLABELED AS A 4" SANITARY. PLEASE CORRECT |
| AND SHOW THE CORRECT LOCATION OF THE 4" SANITARY- |
| SECTION 107.2.1 WPB. |
| |
| 7) P-101: CLEANOUT REQUIRED AT 3" SD |
| VERTICAL/HORIZONTAL TRANSITION- 1101.8, 708.1.4, |
| 708.1.10 FBC P AND P3005.2.4, AND P3005.2.10 FBC RES. |
| |
| 8) P-101: PLEASE PROVIDE A DETAIL FOR THE CERD SHOWN AT |
| THE ESD TERMINATION LOCATIONS- SECTION 107.2.1 WPB. |
| |
| 9) P-101: REQUIRED VENT NOT SHOWN AT P-2A- SECTION |
| P3101.2.1 FBC RES. |
| |
| 10) P-102: CLEANOUTS REQUIRED AT 3" SD VERT/HOR. |
| TRANSITIONS ON EXTERIOR WALLS, AND SD, ESD AND |
| CONDENSATE LINE VERT/HOR. TRANSITIONS SHOWN AT INTERIOR |
| WALLS- SECTIONS 1101.8, 708.1.4, 708.1.10 FBC P AND |
| P3005.2.4, AND P3005.2.10 FBC RES. |
| |
| 11) P-103: CLEANOUTS REQUIRED AT 3" SD |
| VERTICAL/HORIZONTAL TRANSITION- 1101.8, 708.1.4, |
| 708.1.10 FBC P AND P3005.2.4, AND P3005.2.10 FBC RES. |
| |
| 12) P-104: PLEASE CONFIRM WATER CANNOT BECOME ENTRAPPED |
| IN THE OPEN AREA BY THE SECOND FLOOR GYM IF THE SLOT |
| DRAIN WAS TO BE BLOCKED. OTHERWISE PROVIDE AN EMERGENCY |
| ROOF DRAIN- SECTION 1108.1 FBC P. |
| |
| 13) P-105: INDICATE HOW ACCESS WILL BE PROVIDED TO THE |
| WATER BALANCING VALVES- SECTION P2903.9.3. |
| |
| 14) P-106 & P-107: INDICATE HOW THE UNDERGROUND WATER |
| PIPING WILL BE PROTECTED FROM CORROSION- SECTIONS |
| P2903.2.1 & P2903.3. |
| |
| 15) P-200: PLEASE ADD THE HOSE BIBS TO THE PLUMBING |
| FIXTURE CONNECTION SCHEDULE- P2903.10 FBC RES. A) |
| PLEASE CORRECT NOTE 2 UNDER THE SCHEDULE REFERENCING A |
| MIAMI-DADE COUNTY ORDINANCE- SECTION 107.2.1 WPB. |
| |
| 16) P-200: PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR |
| THE GAS AND ELECTRIC WATER HEATERS AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- SECTIONS P2801.3 AND |
| M2005.1 FBC RES. CORRECT THE ENERGY COMPLIANCE REPORT |
| R405-2017 INDICATES ONE GAS-FIRED HEATER, THREE ARE |
| SHOWN ON THE SHEET P-105. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |