2020-08-11 10:50:27 | NEW SFR |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) CODE SECTION SHOWN ON THE STAIR SECTION DRAWINGS FOR |
| THE STAIR HANDRAILS IS INCORRECT FBC R311.7.7 SHOULD BE |
| FBC R311.7.8 |
| 2) DOOR FROM GARAGE LABELED (120) CANNOT OPEN INTO THE |
| BEDROOM PER FBC R302.5.1 |
| 3) DOOR SCHEDULE SHOWS 2 TYPE (F) DOORS - PLEASE |
| CLARIFY THE DOOR TYPE FROM GARAGE TO LIVING SPACE TO |
| COMPLY WITH FBC R302.5.1 |
| 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE INSTALLED |
| - OR - PROVIDE A STATEMENT ON THE DRAWINGS AS TO THE |
| REFERRAL OF THE ROOFING SYSTEM PER FBC WPB AMENDMENTS |
| 107.3.4.1 DEFERRED SUBMITTAL. |
| 5) THE PROVIDED STORM WATER CALCULATIONS NEED TO BE |
| SIGNED AND DATED BY THE ENGINEER. |
| 6) SHOW THE REQUIRED FLOOD VENTS IN THE GARAGES PER FBC |
| R322.2.2 |
| 7) DRAWINGS AND DOCUMENTS DO NOT SHOW IN "ADOBE READER" |
| AS DIGITALLY/ELECTRONICALLY SIGNED. "ADOBE READER" |
| STATES "AT LEAST ONE SIGNATURE HAS PROBLEMS". PLEASE |
| CHECK TO SEE THAT THE ELECTRONIC SIGNATURES ARE CARRIED |
| OVER PROPERLY. SIGNED AND SEALED DRAWINGS AND DOCUMENTS |
| IN PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY |
| SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN |
| ELECTRONIC PLAN REVIEW. |
| |
| |