Plan Review Notes
Plan Review Notes For Permit 20070078
Permit Number 20070078
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-11 10:50:27NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE SECTION SHOWN ON THE STAIR SECTION DRAWINGS FOR
 THE STAIR HANDRAILS IS INCORRECT FBC R311.7.7 SHOULD BE
 FBC R311.7.8
 2) DOOR FROM GARAGE LABELED (120) CANNOT OPEN INTO THE
 BEDROOM PER FBC R302.5.1
 3) DOOR SCHEDULE SHOWS 2 TYPE (F) DOORS - PLEASE
 CLARIFY THE DOOR TYPE FROM GARAGE TO LIVING SPACE TO
 COMPLY WITH FBC R302.5.1
 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE INSTALLED
 - OR - PROVIDE A STATEMENT ON THE DRAWINGS AS TO THE
 REFERRAL OF THE ROOFING SYSTEM PER FBC WPB AMENDMENTS
 107.3.4.1 DEFERRED SUBMITTAL.
 5) THE PROVIDED STORM WATER CALCULATIONS NEED TO BE
 SIGNED AND DATED BY THE ENGINEER.
 6) SHOW THE REQUIRED FLOOD VENTS IN THE GARAGES PER FBC
 R322.2.2
 7) DRAWINGS AND DOCUMENTS DO NOT SHOW IN "ADOBE READER"
 AS DIGITALLY/ELECTRONICALLY SIGNED. "ADOBE READER"
 STATES "AT LEAST ONE SIGNATURE HAS PROBLEMS". PLEASE
 CHECK TO SEE THAT THE ELECTRONIC SIGNATURES ARE CARRIED
 OVER PROPERLY. SIGNED AND SEALED DRAWINGS AND DOCUMENTS
 IN PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY
 SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN
 ELECTRONIC PLAN REVIEW.
  
  