Plan Review Notes
Plan Review Notes For Permit 20070049
Permit Number 20070049
Review Stop B
Sequence Number 5
Notes
Date Text
2020-08-19 14:34:41WINDOWS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 5TH REVIEW - PLEASE READ THE CORRECTION COMMENTS
 CAREFULLY
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE ENGINEERING SUPPLIED SHOWING THE WIND DESIGN
 PRESSURES FROM "ENGINEERING EXPRESS" SHOWS THE REQUIRED
 POSITIVE PRESSURES AT (+58.9) THE PRODUCT APPROVALS FOR
 THE SNGLE HUNG AND THE FIXED GLASS SHOW A MAXIMUM
 PRESSURE OF (+55) - PLEASE PROVIDE PRODUCT APPROVALS
 THAT MEET OR EXCEED THE REQUIRED WIND DESIGN PRESSURES
 SHOWN ON THE "ENGINEERING EXPRESS" DOCUMENT PROVIDED.
 2) THE SIGNED AND SEALED ENGINEERING FROM "ENGINEERING
 EXPRESS" =
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.