2020-07-15 14:51:11 | WINDOWS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) THE ENGINEERING SUPPLIED SHOWING THE WIND DESIGN |
| PRESSURES FROM "ENGINEERING EXPRESS" SHOWS THE REQUIRED |
| POSITIVE PRESSURES AT (+58.9) THE PRODUCT APPROVALS FOR |
| THE SNGLE HUNG AND THE FIXED GLASS SHOW A MAXIMUM |
| PRESSURE OF (+55) - PLEASE PROVIDE PRODUCT APPROVALS |
| THAT MEET OR EXCEED THE REQUIRED WIND DESIGN PRESSURES. |
| 2) THE SIGNED AND SEALED ENGINEERING FROM "ENGINEERING |
| EXPRESS" = |
| SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG |
| WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS |
| MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN |
| REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING |
| DEPT.) |
| |
| |