Plan Review Notes
Plan Review Notes For Permit 20070034
Permit Number 20070034
Review Stop G
Sequence Number 2
Notes
Date Text
2020-07-30 16:17:2907/30/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ACCORDING TO CITY RECORDS A PERMIT WAS APPLIED FOR
 IN JANUARY 10, 2019 #1910365 AND NO WORK WAS EVER
 PERMITTED OR INSPECTED, THE PERMIT WAS REVOKED. AT THIS
 TIME, WE REQUIRE FOR THE WHOLE SYSTEM TO BE ADDED TO
 THE EXISTING PERMIT ON FILE FOR A FULL EVALUATION AT
 THE HOMEOWNER EXPENSE.
 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (RANGE
 AND DRYER IF APPLICABLE) TO VERIFY COMPLIANCE WITH 2017
 FBC RES. SEC. G2408.1.
  
 4. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS AT 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 5. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 6. LABEL DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2.
  
 7. HOT WATER LINE NOT IN CONDITION SPACE NEED TO BE
 INSULATED PER THE 2017 FBC RE SEC RE 403.5.3.
  
 8. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC
 RES. SEC. G2401.1.3.
  
 9. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1
  
 10. THE OLD WATER HEATER IS IN A STORAGE ROOM AND IT
 STATES THAT IT WILL BE CAPPED OFF BUT PLEASE CLARIFY IF
 THE VENT THROUGH THE ROOF WILL ALSO BE SEALED OR
 COVERED AGAINST RODENT INVASION PER THE 2017 FBC SEC. R
 2606.1.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW