2020-07-30 16:17:29 | 07/30/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. ACCORDING TO CITY RECORDS A PERMIT WAS APPLIED FOR |
| IN JANUARY 10, 2019 #1910365 AND NO WORK WAS EVER |
| PERMITTED OR INSPECTED, THE PERMIT WAS REVOKED. AT THIS |
| TIME, WE REQUIRE FOR THE WHOLE SYSTEM TO BE ADDED TO |
| THE EXISTING PERMIT ON FILE FOR A FULL EVALUATION AT |
| THE HOMEOWNER EXPENSE. |
| 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (RANGE |
| AND DRYER IF APPLICABLE) TO VERIFY COMPLIANCE WITH 2017 |
| FBC RES. SEC. G2408.1. |
| |
| 4. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND |
| THE SERVICE METER DISCHARGES IS AT 12" WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| SEC. G2421.1. |
| |
| 5. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| |
| 6. LABEL DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 |
| FBC RES. SEC. G2419.2. |
| |
| 7. HOT WATER LINE NOT IN CONDITION SPACE NEED TO BE |
| INSULATED PER THE 2017 FBC RE SEC RE 403.5.3. |
| |
| 8. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS |
| ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC |
| RES. SEC. G2401.1.3. |
| |
| 9. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 105.1 |
| |
| 10. THE OLD WATER HEATER IS IN A STORAGE ROOM AND IT |
| STATES THAT IT WILL BE CAPPED OFF BUT PLEASE CLARIFY IF |
| THE VENT THROUGH THE ROOF WILL ALSO BE SEALED OR |
| COVERED AGAINST RODENT INVASION PER THE 2017 FBC SEC. R |
| 2606.1. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |