Plan Review Notes For Permit 20070030 |
Permit Number |
20070030 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-09-23 14:01:06 | SEPARATE PERMIT REQUIRED FOR GAS PIPING TO THE TANKLESS | | WATER HEATERS, THE RANGE, AND THE VENTLESS FIREPLACES. | | COMPLETE PLANS ARE REQUIRED INCLUDING A GAS RISER | | DRAWING, SPECS FOR ALL APPLIANCES AND EQUIPMENT, | | VENTING PLANS , AND THE COMBUSTION AIR CALCULATIONS ON | | SHEET P103 SHALL ALSO BE SUBMITTED UNDER THE GAS PIPING | | PERMIT. | | PLEASE NOTE THAT A REVIEW OF THE GAS PLANS AND | | SPECIFCATIONS WAS NOT COMPLETED AT THIS TIME HOWEVER | | THE SUBMITTED SPECS FOR THE RANGE INDICATE A HIGHER | | BTUH LOAD THAN THE LOAD SHOWN ON THE GAS RISER DRAWING- | | SHEET P103. |
|