2020-09-09 13:45:232ND REVIEW FBC-2017 RES.
 PERMIT- 20070030
 9/9/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1ST REVIEW COMMENTS #5, 6, 8, 9, 10, 11 PRINTED BELOW
 HAVE NOT BEEN COMPLETED ADDRESSED.
  
 5) P100 & P102: THE 3" STACK CANNOT SERVE AS THE WET
 VENT FOR THE POWDER ROOM WATER CLOSET AND LAVATORY-
 SECTION P3108.2 FBC RES. THE WATER CLOSET IS NOT
 VENTED.
  
 6) P100 & P102: NO VENT IS SHOWN FOR THE ICE MAKER
 TRAP- SECTION P3101.2.1 & P3105.1. THE REVISED DRAWING
 DOES NOT SHOW A VENT FOR THE TRAP.
  
 8) P101 & P102: THE RISER SHOWS AN INCORRECT 2"
 HORIZONTAL DRAIN EXTENDING FROM THE 3" LAUNDRY WASTE
 STACK TO THE MAIN DRAIN- A MINIMUM 3" DRAIN IS
 REQUIRED- SECTION P3005.1.6. A 3" STACK VENT FOR THE 3"
 WASTE STACK SHALL BE PROVIDED PER SECTION P3109.3 FBC
 RES. THE 2" DRY VENT EXTENDING FROM THE MUD ROOM SINK
 SHALL NOT CONNECT HORIZONTALLY INTO THE WASTE STACK AT
 A POINT BELOW THE 2ND FLOOR CLOTHES WASHER DRAIN
 CONNECTION- SECTIONS P3109.3 AND P3104.5.
  
 9) P100 & P102: THE DRY VENT FOR THE WET VENT SERVING
 BATH 109 THAT IS EXTENDING FROM THE SHOWER DRAIN SHALL
 EXTEND TO THE OPEN AIR- SECTIONS P3108.2.1 & P3104.1.
 THE DRY VENT FROM BATH 109 LAV AND SHALL NOT CONNECT
 INTO THE 3" SOIL STACK BECAUSE OF POSSIBLE BLOCKAGE OF
 THE LAV VENT-SECTION P3104.5. THE REVISED PLAN SHOWS A
 2" VTR FOR THE FIXTURES WHICH IS CODE COMPLIANT.
  
 10) PROVIDE A WATER RISER DRAWING- SECTION 107.3.5.3
 WPB. PLEASE INCLUDE IN THE RISER THE LOCATIONS OF
 SHUTOFF VALVES, WATER HAMMER ARRESTORS, AND BACKFLOW
 PREVENTERS WHERE REQUIRED- SECTIONS P2902.3 & P2903.5.
 REFER TO SECTION R403.5.1 FBC EC: CIRCULATION PUMPS FOR
 HEATED WATER CIRCULATION SYSTEMS ARE NOT OPTIONAL.
 PLEASE CORRECT NOTE #5 ON SHEET P106 AND VERIFY THE NEW
 AO SMITH WATER HEATERS WILL BE EQUIPPED WITH INTEGRAL
 CIRCULATION PUMPS.
  
 11) PROVIDE EQUIPMENT SCHEDULES FOR THE WATER HEATERS
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS SECTIONS
 P2801.3 & G2448.1. PLEASE SHOW THE LOCATIONS OF THE
 WATER HEATERS ON THE PLUMBING FLOOR PLAN DRAWINGS.
 PLEASE NOTE THAT THE GAS PIPING INSTALLATIONS SHALL BE
 UNDER SEPARATE PERMIT- SECTIONS 105.3 & 107.1 WPB (SEE
 GAS COMMENTS FOR FURTHER INFORMATION). PLEASE NOTE THAT
 COMPLIANCE DATA FOR THE WATER HEATERS SHALL BE LISTED
 IN THE REQUIRED ENERGY COMPLIANCE REPORT- SEE TABLE
 C404.2 FBC EC. MANUFACTURER'S SPECIFICATIONS FOR THE
 WATER HEATERS WERE NOT SUBMITTED. PLEASE SUBMIT SPECS
 INCLUDING TEMPERATURE RISE AND GPM FLOW SIZING CHARTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  