2020-09-09 13:45:23 | 2ND REVIEW FBC-2017 RES. |
| PERMIT- 20070030 |
| 9/9/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1ST REVIEW COMMENTS #5, 6, 8, 9, 10, 11 PRINTED BELOW |
| HAVE NOT BEEN COMPLETED ADDRESSED. |
| |
| 5) P100 & P102: THE 3" STACK CANNOT SERVE AS THE WET |
| VENT FOR THE POWDER ROOM WATER CLOSET AND LAVATORY- |
| SECTION P3108.2 FBC RES. THE WATER CLOSET IS NOT |
| VENTED. |
| |
| 6) P100 & P102: NO VENT IS SHOWN FOR THE ICE MAKER |
| TRAP- SECTION P3101.2.1 & P3105.1. THE REVISED DRAWING |
| DOES NOT SHOW A VENT FOR THE TRAP. |
| |
| 8) P101 & P102: THE RISER SHOWS AN INCORRECT 2" |
| HORIZONTAL DRAIN EXTENDING FROM THE 3" LAUNDRY WASTE |
| STACK TO THE MAIN DRAIN- A MINIMUM 3" DRAIN IS |
| REQUIRED- SECTION P3005.1.6. A 3" STACK VENT FOR THE 3" |
| WASTE STACK SHALL BE PROVIDED PER SECTION P3109.3 FBC |
| RES. THE 2" DRY VENT EXTENDING FROM THE MUD ROOM SINK |
| SHALL NOT CONNECT HORIZONTALLY INTO THE WASTE STACK AT |
| A POINT BELOW THE 2ND FLOOR CLOTHES WASHER DRAIN |
| CONNECTION- SECTIONS P3109.3 AND P3104.5. |
| |
| 9) P100 & P102: THE DRY VENT FOR THE WET VENT SERVING |
| BATH 109 THAT IS EXTENDING FROM THE SHOWER DRAIN SHALL |
| EXTEND TO THE OPEN AIR- SECTIONS P3108.2.1 & P3104.1. |
| THE DRY VENT FROM BATH 109 LAV AND SHALL NOT CONNECT |
| INTO THE 3" SOIL STACK BECAUSE OF POSSIBLE BLOCKAGE OF |
| THE LAV VENT-SECTION P3104.5. THE REVISED PLAN SHOWS A |
| 2" VTR FOR THE FIXTURES WHICH IS CODE COMPLIANT. |
| |
| 10) PROVIDE A WATER RISER DRAWING- SECTION 107.3.5.3 |
| WPB. PLEASE INCLUDE IN THE RISER THE LOCATIONS OF |
| SHUTOFF VALVES, WATER HAMMER ARRESTORS, AND BACKFLOW |
| PREVENTERS WHERE REQUIRED- SECTIONS P2902.3 & P2903.5. |
| REFER TO SECTION R403.5.1 FBC EC: CIRCULATION PUMPS FOR |
| HEATED WATER CIRCULATION SYSTEMS ARE NOT OPTIONAL. |
| PLEASE CORRECT NOTE #5 ON SHEET P106 AND VERIFY THE NEW |
| AO SMITH WATER HEATERS WILL BE EQUIPPED WITH INTEGRAL |
| CIRCULATION PUMPS. |
| |
| 11) PROVIDE EQUIPMENT SCHEDULES FOR THE WATER HEATERS |
| AND SUBMIT MANUFACTURER'S SPECIFICATIONS SECTIONS |
| P2801.3 & G2448.1. PLEASE SHOW THE LOCATIONS OF THE |
| WATER HEATERS ON THE PLUMBING FLOOR PLAN DRAWINGS. |
| PLEASE NOTE THAT THE GAS PIPING INSTALLATIONS SHALL BE |
| UNDER SEPARATE PERMIT- SECTIONS 105.3 & 107.1 WPB (SEE |
| GAS COMMENTS FOR FURTHER INFORMATION). PLEASE NOTE THAT |
| COMPLIANCE DATA FOR THE WATER HEATERS SHALL BE LISTED |
| IN THE REQUIRED ENERGY COMPLIANCE REPORT- SEE TABLE |
| C404.2 FBC EC. MANUFACTURER'S SPECIFICATIONS FOR THE |
| WATER HEATERS WERE NOT SUBMITTED. PLEASE SUBMIT SPECS |
| INCLUDING TEMPERATURE RISE AND GPM FLOW SIZING CHARTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |