Plan Review Notes
Plan Review Notes For Permit 20070030
Permit Number 20070030
Review Stop E
Sequence Number 2
Notes
Date Text
2020-09-13 14:32:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 1. SERVICE ENTRANCE CONDUCTOR SIZE HAS BEEN CORRECTED
 BUT NOW #350MCM FEEDERS ARE SHOWN TO 200AMP PANEL"A"
 THEN ANOTHER 100AMP PANEL "B" BEING FED FROM 200AMP
 PANEL "A". AMPERAGE FOR 200AMP PANEL CANNOT EXCEED
 200AMPS. PROVIDE LOAD CALCULATION FOR 200AMP PANEL
 INCLUDING LOAD FROM 100AMP SUB-PANEL. NEC 220, FBC
 107.2.1
  
 INFORMATIONAL NOTE: PERHAPS AN MDP PANEL WITH A 200A
 OCP FEEDER TO PANEL "A" AND A 100A OCP FEEDER TO PANEL
 "B"??? *** ONLY A SUGGESTION*** ANY CODE COMPLIANT
 DESIGN WILL SUFFICE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved