2020-08-03 15:48:191ST REVIEW FBC-2017 RES.
 PERMIT- 20070030
 8/3/2020\
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P100, P101, & P102 CABANA BATH AND BATH #4:
 THE DISTANCES FROM THE SHOWER DRAIN TRAPS TO THE COMMON
 VENT APPEAR TO EXCEED THE MAXIMUM 6" ALLOWABLE DISTANCE
 PER TABLE P3105.1 FBC RES.
  
 2) P100 & P102: THE COMMON VENT FOR THE SINKS AT THE
 WET BAR AND BUTLER'S PANTRY SHALL EXTEND TO THE OPEN
 AIR- SECTION P3104.1.
  
 3) P100 & P102: PROVIDE A VTR SYMBOL FOR THE AT THE
 CONNECTION OF THE TWO VENT STACKS RISING FROM BATH #3 &
 4- SECTIONS P3102.1 & P3104.1.
  
 4) P101 & P102: VERIFY THE SHOWER DRAIN IN BATH #3 WILL
 CONNECT TO THE VERTICAL VENT ABOVE OR AT THE SAME
 ELEVATION AS THE TWO WATER CLOSETS- SECTION P3108.4.
  
 5) P100 & P102: THE 3" STACK CANNOT SERVE AS THE WET
 VENT FOR THE POWDER ROOM WATER CLOSET AND LAVATORY-
 SECTION P3108.2.
  
 6) P100 & P102: NO VENT IS SHOW FOR THE ICE MAKER TRAP-
 SECTION P3101.2.1 & P3105.1.
  
 7) P101 & P102 MASTER BATH: THE DISTANCE FROM THE
 SHOWER DRAIN TRAP TO THE COMMON VENT APPEARS TO EXCEED
 THE MAXIMUM 6" ALLOWABLE DISTANCE PER TABLE P3105.1 FBC
 RES. IF THE INTENTION IS THE WET VENT THE SHOWER PLEASE
 NOTE THAT NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN
 SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 DRAIN CONNECTION. THE DRAWING SHOWS TWO.
  
 8) P101 & P102: THE RISER SHOWS AN INCORRECT 2"
 HORIZONTAL DRAIN EXTENDING FROM THE 3" LAUNDRY WASTE
 STACK TO THE MAIN DRAIN- A MINIMUM 3" DRAIN IS
 REQUIRED- SECTION P3005.1.6.
  
 9) P100 & P102: THE DRY VENT FOR THE WET VENT SERVING
 BATH 109 THAT IS EXTENDING FROM THE SHOWER DRAIN SHALL
 EXTEND TO THE OPEN AIR- SECTIONS P3108.2.1 & P3104.1.
  
 10) PROVIDE A WATER RISER DRAWING- SECTION 107.3.5.3
 WPB. PLEASE INCLUDE IN THE RISER THE LOCATIONS OF
 SHUTOFF VALVES, WATER HAMMER ARRESTORS, AND BACKFLOW
 PREVENTERS WHERE REQUIRED- SECTIONS P2902.3 & P2903.5.
  
 11) PROVIDE EQUIPMENT SCHEDULES FOR THE WATER HEATERS
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS SECTIONS
 P2801.3 & G2448.1. PLEASE SHOW THE LOCATIONS OF THE
 WATER HEATERS ON THE PLUMBING FLOOR PLAN DRAWINGS.
 PLEASE NOTE THAT THE GAS PIPING INSTALLATIONS SHALL BE
 UNDER SEPARATE PERMIT- SECTIONS 105.3 & 107.1 WPB (SEE
 GAS COMMENTS FOR FURTHER INFORMATION) .PLEASE NOTE THAT
 COMPLIANCE DATA FOR THE WATER HEATERS SHALL BE LISTED
 IN THE REQUIRED ENERGY COMPLIANCE REPORT- SEE TABLE
 C404.2 FBC EC.
  
 12) A100 & A102: PROVIDE COMPLETE DIMENSIONS FOR THE
 SHOWERS ON THE PLAN AND PROVIDE SHOWER PAN DETAILS PER
 SECTIONS P2708.1 & P2709.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  