2020-08-03 16:12:20 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 20070030 | | 8/3/2020 | | | | CODES IN EFFECT: | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P103: THE GAS PIPING INSTALLATIONS FOR THE | | RESIDENCE SHALL BE UNDER A SEPARATE PERMIT, HOWEVER THE | | PLANS DO NOT PROVIDE COMBUSTION AIR CALCULATIONS OR | | VENTING PLANS FOR THE FIREPLACES AND THE GAS RANGE- SEE | | SECTIONS G2407.1 & G2427.1 FBC RES. PLEASE NOTE THAT | | COMPLETE GAS PIPING PLANS UNDER SEPARATE PERMIT SHALL | | INCLUDE THE RISER DRAWING, THE CORRECT PIPE SIZING | | TABLES FROM THE FBC RES, AND SPECIFICATIONS FOR THE | | REGULATORS AND ALL GAS-FIRED APPLIANCES AND EQUIPMENT. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | CCOLE@WPB | | |
|