Plan Review Notes
Plan Review Notes For Permit 20070020
Permit Number 20070020
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-07 09:50:402ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20070020
 8/7/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE
 MARKED AS PASSED OR FAILED. ADDITIONAL NOTES IN CAPITOL
 LETTERS WILL ADDED TO FAILED COMMENTS.
  
 1) FAILED. SHEETS T, A210, & P1.1: REFER TO SECTION
 211.1.2 FBC ACC, AND TABLE 404.3 FBC P- NO FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH SECTIONS 602.1 - 602.6 FBC
 ACC, AND ONE SHALL COMPLY WITH 602.7. SECTION 602.7
 REQUIRES THAT SPOUT OUTLETS FOR STANDING PERSONS SHALL
 BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM FROM THE
 FINISHED FLOOR. REVISE THE PLANS TO SHOW THE LOCATIONS
 OF THE FOUNTAINS AND PROVIDE THESE DETAILS: THE FIXTURE
 CALCULATIONS ON SHEET (T) INDICATE 2 DRINKING FOUNTAINS
 PROVIDED, HOWEVER ONLY ONE IS SHOWN ON SHEET A010.
 SHEET A310 SHOWS ELEVATION DRAWINGS MEETING COMPLIANCE
 WITH B.
 A) FAILED. THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS
 FOR FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC
 ACC. NOT PROVIDED
 B) PASSED. KNEE AND TOE CLEARANCES- SECTION 306.
 C) FAILED. SPOUT HEIGHT AND SPOUT LOCATION- SECTION
 602.4 AND 602.5. ALLOWABLE SPOUT HEIGHTS DESIGNATIONS
 ARE SHOWN ABOVE THE SPOUTS- PLEASE CORRECT.
  
 2) PASSED. SHEETS T, A210, AND P1.1: SHOW THE LOCATION
 OF THE SERVICE SINK AND LABEL IT AS EITHER NEW OR
 EXISTING- TABLE 403.3 FBC P.
  
 3) PASSED. A210: PLEASE LABEL THE TOILET ROOMS AS MALE,
 FEMALE OR UNISEX- SEE SECTIONS 403.2 & 403.2.1 FBC-P.
  
 4) FAILED. A210: PROVIDE A DETAIL FOR THE COUNTERTOP
 AND SINK REPLACEMENT IN THE EXAM ROOM- SECTIONS 212.3 &
 606.1- 606.5 FBC ACC. DETAIL 3/A310 DOES NOT SHOW
 REQUIRED 34" HEIGHT TO THE SINK RIM OR COUNTER SURFACE
 FROM THE F.F.
  
 5) FAILED. A210: THE FINISH SCHEDULE INDICATES
 NON-COMPLIANCE FOR THE WALLS. PLEASE SEE SECTION 310.3
 FBC P AND SECTION 1210.2.2 FBC B. AND PROVIDE A SMOOTH,
 HARD, NON-ABSORBENT MATERIAL WHERE REQUIRED DRY WALL IS
 NOT CLASSIFIED AS A HARD NON -ABSORBENT MATERIAL AND
 ADDING THE PAINT DOES NOT MAKE IT COMPLIANT. PLEASE
 READ THE EXCERPT BELOW:
 INTERNATIONAL CODE: 2015 INTERNATIONAL BUILDING CODE
 SECTION: 1210.2.2
 QUESTION: SECTION 1210.2.2 SPECIFIES THAT WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. DOES
 PAINT OVER DRYWALL QUALIFY AS SMOOTH, HARD,
 NONABSORBENT SURFACE?
 ANSWER: SECTION 1210.2.2 STIPULATES THAT THE MATERIAL
 BE "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 6) PASSED. A310: THE HEIGHT OF THE GRAB BARS SHALL BE
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. THE PLAN SHOWS THE MEASUREMENT TO THE
 CENTERLINE OF THE BARS- PLEASE CORRECT.
  
 7) PASSED. P0.1 & P1.1: INDICATE HOW HOT WATER IS BEING
 PROVIDED TO THE MOP SINK, AND HOW TEMPERED WATER IS
 BEING PROVIDED TO THE LAVATORY PER SECTIONS 416.5 &
 607.1 FBC P. PLEASE NOTE THAT TEMPERED SHALL BE
 SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070- SECTION 607.1.2 FBC P.
 VERIFY THAT THE EWH UNDER THE SINK WILL NOT OBSTRUCT
 REQUIRED KNEE AND TOE CLEARANCES AS SHOWN ON SHEET
 A310.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB.
  