2020-07-17 13:54:11 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20070020 |
| 7/17/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS T, A210, & P1.1: REFER TO SECTION 211.1.2 FBC |
| ACC, AND TABLE 404.3 FBC P- NO FEWER THAN TWO DRINKING |
| FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| SHALL COMPLY WITH SECTIONS 602.1 - 602.6 FBC ACC, AND |
| ONE SHALL COMPLY WITH 602.7. SECTION 602.7 REQUIRES |
| THAT SPOUT OUTLETS FOR STANDING PERSONS SHALL BE 38 |
| INCHES MINIMUM AND 43 INCHES MAXIMUM FROM THE FINISHED |
| FLOOR. REVISE THE PLANS TO SHOW THE LOCATIONS OF THE |
| FOUNTAINS AND PROVIDE THESE DETAILS: |
| A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| B) KNEE AND TOE CLEARANCES- SECTION 306. |
| C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND |
| 602.5. |
| |
| 2) SHEETS T, A210, AND P1.1: SHOW THE LOCATION OF THE |
| SERVICE SINK AND LABEL IT AS EITHER NEW OR EXISTING- |
| TABLE 403.3 FBC P. |
| |
| 3) A210: PLEASE LABEL THE TOILET ROOMS AS MALE, FEMALE |
| OR UNISEX- SEE SECTIONS 403.2 & 403.2.1 FBC-P. |
| |
| 4) A210: PROVIDE A DETAIL FOR THE COUNTERTOP AND SINK |
| REPLACEMENT IN THE EXAM ROOM- SECTIONS 212.3 & 606.1- |
| 606.5 FBC ACC. |
| |
| 5) A210: THE FINISH SCHEDULE INDICATES NON-COMPLIANCE |
| FOR THE WALLS. PLEASE SEE SECTION 310.3 FBC P AND |
| SECTION 1210.2.2 FBC B. AND PROVIDE A SMOOTH, HARD, |
| NON-ABSORBENT MATERIAL WHERE REQUIRED. |
| |
| 6) A310: THE HEIGHT OF THE GRAB BARS SHALL BE 33 INCHES |
| MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE PLAN |
| SHOWS THE MEASUREMENT TO THE CENTERLINE OF THE BARS- |
| PLEASE CORRECT. |
| |
| 7) P0.1 & P1.1: INDICATE HOW HOT WATER IS BEING |
| PROVIDED TO THE MOP SINK, AND HOW TEMPERED WATER IS |
| BEING PROVIDED TO THE LAVATORY PER SECTIONS 416.5 & |
| 607.1 FBC P. PLEASE NOTE THAT TEMPERED SHALL BE |
| SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| THAT CONFORMS TO ASSE 1070- SECTION 607.1.2 FBC P. |
| VERIFY THAT THE EWH UNDER THE SINK WILL NOT OBSTRUCT |
| REQUIRED KNEE AND TOE CLEARANCES AS SHOWN ON SHEET |
| A310. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |