Plan Review Notes
Plan Review Notes For Permit 20070017
Permit Number 20070017
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-07-14 12:09:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM
 OVER.
  
 THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS
 THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN.
  
 PLEASE PROVIDE CALCULATIONS DETAILS OR PROVIDE A
 STATEMENT THAT THE SYSTEM DESIGN SHALL NOT BE AFFECTED
 BY THE ADDITION OF FLEX HEADS ANF THE ENTIRE SYSTEM
 SHALL FUNCTION IN ACCORDANCE WITH NFPA 13 AND OTHER
 APPLICABLE CODES.
  
  
  
 2) THE SPEC SHEETS NOR PLAN SHEETS INDICATE WHICH TYPE
 AND/OR SIZE OF THE FLEX DROP SPRINKLERS ARE BEING USED.
  
 PLEASE PROVIDE SHEETS THAT MATCH THE NEW HYDRAULIC
 CALCULATIONS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL