Plan Review Notes
Plan Review Notes For Permit 20061539
Permit Number 20061539
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-21 19:01:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COMPLIANCE WITH FBC EC 405.2.5 FOR EXTERIOR
 LIGHTING. LIGHTING MUST BE CONTROLLED BY TIMER SWITCH
 CAPABLE OF RETAINING THE HOME TIME SETTING FOR AN EVENT
 OF UP TO 10 HOURS AFTER A LOSS OF POWER. A NOTE ON PLAN
 WILL SUFFICE.
  
 2. DISCONNECT MUST BE WITHIN SIGNT OF SIGN. 600.6A1 NEC
  
 3. JBOX AND BRANCH CIRCUIT "BY OTHERS" SHOWS LOW
 VOLTAGE AND HIGH VOLTAGE IN SAME JBOX. PROVIDE
 CORRECTION. NEC 725.136B
  
 4. REFERENCE PERMIT NUMBER FOR BRANCH CIRCUIT AND
 DISCONNECT THAT IS REQUIRED TO POWER SIGN, TO BE DONE
 "BY OTHERS" AS ANNOTATED ON PLAN. CIRCUIT MUST BE RAN
 BY LICENSED ELECTRICIAN.
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 5. PLAN IS DIGITALLY SIGNED BUT THERE IS NO 3RD PARTY
 VERIFICATION CERTIFICATE FOR DIGITAL SIGNATURE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  