Plan Review Notes For Permit 20061524 |
Permit Number |
20061524 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-10 10:35:36 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | 1-- FLAT ROOF NOA 20-0131.01 SUBMITTED: SELECTED | | ASSEMBLY ON PAGE 12 OF 18 DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED | | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER | | AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 | | ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE | | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1 | | FBC-RESIDENTIAL. | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|