Plan Review Notes
Plan Review Notes For Permit 20061471
Permit Number 20061471
Review Stop Z
Sequence Number 2
Notes
Date Text
2020-09-11 16:45:18FAILED
  
 ARCADE IDENTITY SIGN - TYPE 1D OPTION C SUSPENDED PANEL
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE CITYPLACE MANAGEMENT APPROVAL STAMP IS REQUIRED
 ON THE PLANS. WHILE THE RESPONSE COMMENT STATES THAT
 THIS IS PROVIDED, STAFF IS UNABLE TO LOCATE STAMPED
 PLANS OR A LETTER FROM CITYPLACE RETAIL APPROVING THE
 PLANS IN THE RESUBMITTAL DOCUMENTS.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA APPROVED ON
 SEPTEMBER 8, 2020, REQUIRE THAT THE SIGN COPY AREA
 SHALL MAINTAIN A MARGIN AT LEAST THREE (3) INCHES FROM
 ANY EDGE OF THE PERCEIVED SIGN AREA. THE PLANS
 SUBMITTED WITH THE PERMIT PROVIDE THE DIMENSION OF THE
 SIGN AND THE DIMENSION OF THE COPY AREA; HOWEVER THE
 DIMENSION FROM THE COPY AREA TO EACH SIGN EDGE IN NOT
 PROVIDED. WHILE THE OVERALL DIFFERENCE IN THE COPY AND
 SIGN EDGE TOTALS SIX (6) INCHES BOTH VERTICALLY AND
 HORIZONTALLY, SINCE NO DIMENSIONS ARE PROVIDED, STAFF
 CANNOT VERIFY THAT THE SIGN COPY IS CENTERED. NOTE:
 SCALING THE PLANS DOES NOT SHOW AN EQUIDISTANT
 DIMENSION FOR THE COPY BETWEEN THE TOP AND BOTTOM SIGN
 EDGES, WHICH MEANS THERE ARE NOT THREE (3) INCHES FROM
 THE BOTTOM OF THE COPY TO THE EDGE OF THE SIGN. ON
 SEPTEMBER 8, 2020, JORDAN RATHLEV, OF RELATED, SENT
 STAFF A COPY OF THE SIGN PLAN WHICH INCLUDED THE
 DIMENSIONS FROM THE COPY TO THE EDGES OF THE SIGN AND
 SHOWED THAT THE MINIMUM THREE (3) INCHES IS MET FOR ALL
 SIDES. A DIMENSIONED PLAN NEEDS TO BE SUBMITTED WITH
 THE PERMIT.
  
 3) THE PLANS UPLOADED ON SEPTEMBER 8, 2020, WHICH
 INCLUDE THE ENGINEER'S SEAL, DO NOT THE LATEST PLAN
 REVISIONS SUBMITTED TO THE CITY. THE NOTES AND
 DIMENSIONS THAT WERE ADDED TO THE PLANS REVISED ON
 AUGUST 4, 2020, NO LONGER APPEAR. THE PLANS SIGNED BY
 THE ENGINEER HAVE A REVISION DATED OF JUNE 22, 2020. TO
 FURTHER COMPLICATE MATTERS, THE RATHLEV PLANS SHOWING
 THE DIMENSIONS, DO NOT HAVE THE ENGINEER SEAL, NOR DO
 THEY INCLUDE THE ELECTRICAL OR ALL OF THE BUILDING
 NOTES SHOWN ON THE AUGUST 4, 2020 PLANS. SUBMIT PLANS
 THAT SHOW ALL THE NOTES ADDRESSING COMMENTS, ALL THE
 DIMENSIONS AND THAT ARE SEALED.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT RIVETS, SCREWS AND OTHER FASTENERS THAT EXTEND TO
 VISIBLE SURFACES SHALL BE FLUSH, FILLED AND FINISHED SO
 AS TO BE UNNOTICEABLE. THE BOLT HEADS THAT EXTEND PAST
 THE MOUNTING PLATE DO NOT MEET THIS STANDARD. IF THE
 BOLT HEADS MUST EXTEND PAST THE MOUNTING PLATE, THEY
 NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE
 MOUNTING PLATE. ---- THE ORIGINALLY SUBMITTED SHEET 3
 AND THE ENGINEER STAMPED SHEET 3 FAIL TO ADDRESS THIS
 COMMENT. THE AUGUST 4, 2020 SHEET 3 ADDED THE NOTE THAT
 THEY WOULD BE PAINTED BLACK TO MATCH THE MOUNTING
 PLATE. NO DETAILS OR NOTATIONS WERE PROVIDED TO SHOW
 THAT THE BOLT HEADS WILL BE FLUSH TO THE MOUNTING PLATE
 OR FOR STAFF TO VERIFY THE ATTACHMENT METHOD.
  
 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES
 THAT ALL CONDUIT, CROSSOVERS, WIRING NECESSARY FOR THE
 SIGN'S ELECTRICAL CONNECTION TO BE CONCEALED AND NOT
 VISIBLE TO THE PUBLIC. ---- THE AUGUST 4, 2020 SHEET 3
 INCLUDED A NOTE THAT WHILE THE CONDUITS, CROSSOVERS AND
 WIRING REQUIRED FOR THE SIGN IS EXISTING, AD ART WAS TO
 ENSURE THAT FINAL SIGN CONNECTIONS ARE CONCEALED. THIS
 NOTE DOES NOT APPEAR ON THE ENGINEER SIGNED PLANS, SO
 THE PLANS NEED TO BE UPDATED.
  
 6) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT ARCADE IDENTITY SIGNS BE CENTERED WITHIN THE
 ARCADE ARCHWAY. ---- THE AUGUST 4, 2020 SHEET 2
 PROVIDED THE DIMENSIONS TO VERIFY THIS REQUIREMENT. THE
 SEPTEMBER 8, 2020 UPLOADED, ENGINEER SIGNED SHEET 2 NO
 LONGER SHOW THE DIMENSIONS. THIS NEEDS TO BE CORRECTED
 AND RESUBMITTED.
  
 7) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. ---- THE AUGUST 4, 2020 SHEET 3 PROVIDED A NOTE
 TO VERIFY THIS REQUIREMENT. THE NOTE DOES NOT APPEAR ON
 THE SEPTEMBER 8, 2020 UPLOADED ENGINEER SIGNED SHEET 3.
 THIS NEEDS TO BE CORRECTED AND RESUBMITTED.
  
 8) THE BACKER PANEL SETS THE SIZE OF THE SIGN. ----
 NONE OF THE VARIOUS SHEET 3S STATE THE CORRECT SIGN
 SIZE.
  
 PERMITTED: 20.67 SF
 PROPOSED: 12 SF
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  