Plan Review Notes
Plan Review Notes For Permit 20061341
Permit Number 20061341
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-31 13:45:501ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20061341
 7/31/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVIEW THE FIRE DEPT. REVIEW NOTES- NO SITE
 PLAN OR UTILITY PLANS HAVE BEEN SUBMITTED. PLEASE NOTE
 THAT SEPARATE PERMITS WILL BE REQUIRED FOR THE
 UNDERGROUND FIRE LINE AND FOR THE FIRE SERVICE BACKFLOW
 PREVENTER- SECTIONS 105.1 & 107.1 WPB.
  
 2) PROVIDE A SITE PLAN AND A PLUMBING PLAN SHOWING THE
 WATER SERVICE AND SANITARY DRAINAGE SYSTEMS FOR THE
 PROPOSED TRAILER. PROVIDE DETAILS INCLUDING:
  
 A) POTABLE WATER SERVICE PIPE RUN FROM POINT OF
 CONNECTION AT THE CITY MAIN TO THE TEMPORARY TRAILER.
  
 B) TYPE, SIZE AND BURIAL DEPTH OF WATER SERVICE PIPE-
 SECTIONS 602.1, 602.2, 603.1 AND TABLE 605.3 FBC P.
  
 C) BACKFLOW PREVENTER LOCATION AND TYPE TO BE
 INSTALLED. PLEASE NOTE THAT THE BACKFLOW PREVENTER
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT- 608.1.
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC,
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 D) LOCATION AND TYPE OF MAIN SHUTOFF VALVE- 606.1.
  
 E) SANITARY SEWER LINE RUN FROM THE TRAILER TO THE
 POINT OF CONNECTION TO THE CITY SEWER LINE- 701.3.
  
 F) TYPE, SIZE, BURIAL DEPTH OF THE SANITARY SEWER PIPE
 AND LOCATIONS OF CLEANOUTS- TABLE 702.3. AND SECTIONS
 708.1.2 & 708.1.3.
  
 3) PLEASE NOTE IF HOLDING TANKS ARE TO BE INSTALLED FOR
 SANITY SEWER IN LIEU OF CONNECTING TO THE CITY SEWER,
 PLEASE SHOW THEIR LOCATIONS AND SIZES ON THE PLAN AND
 ALL PIPING RUNS. SUBMIT A COPY OF THE CONTRACT FOR THE
 TANKS THAT INCLUDES THE PUMP-OUT SCHEDULE- SECTION
 108.1 WPB.
  
 PLEASE NOTE ADDITIONAL INFORMATION FOR PERMITTING MAY
 BE REQUIRED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 IF YOU HAVE QUESTIONS OR REQUIRE MORE INFORMATION
 PLEASE CONTACT ME OR CHIEF PLUMBING INSPECTOR TIMOTHY
 LARGE- [email protected] (561)-805-6692.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  