2020-07-06 14:32:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS THAT ALL LIFE SAFETY WILL BE
 IN PLACE, TESTED AND INSPECTED PRIOR TO ANY OCCUPANCY.
  
 THE FIRE SPRINKLER AND FIRE ALARM SHALL BE FULLY
 FUNCTIONAL, OPERATIONAL, TESTED AND INSPECTED AS IF IT
 WERE A CO.
  
 A FIRE WATCH IS NOT AN ACCEPTABLE OPTION.
  
 PLEASE REVIEW, ENSURE FUNCTIONALITY AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 1A) WHAT/WHERE IS THE PROPOSED LOCATION OF THE FACP
 DURING THE OCCUPANCY OF PHASE 1 AND FUTURE PHASES?
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
  
 1B) THERE ARE NO INDICATIONS A THE RADIO COMMUNICATIONS
 BEING COMPLETED AND TESTED.
  
 EMERGENCY RADIO COMMUNICATIONS IS A REQUIRED LIFE
 SAFETY SYSTEM.
  
 THE RADIO COMMUNICATIONS IS REQUIRED TO BE INSTALLED,
 INSPECTED AND TESTED ACCORDING TO ALL REQUIRED
 STANDARDS INCLUDING PALM BEACH COUNTY RADIO
 COMMUNICATIONS DEPARTMENT.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEGDEMENT.
  
  
 2) SHEET LS 0.1 - EXITING OUT STAIR # 4 THERE IS AN
 EGRESS PATH OUT ALONG A BARRICADES TO AN UNKNOWN AREA.
  
 WHERE DOES THIS EGRESS LEAD TO? IS THIS AREA A PUBLIC
 WAY?
  
 PER NFPA 101 CH 7
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN
 7.7.1.2 THROUGH 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT
 DISCHARGE SHALL BE OF THE REQUIRED WIDTH AND SIZE TO
 PROVIDE ALL
 OCCUPANTS WITH A SAFE ACCESS TO A PUBLIC WAY.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT IF
 APPLICABLE.
  
  
 2A) SHEET LS 0.1 - WILL THE EXIT FROM THE POOL AREA BY
 THE POOL PAVILION BE ACESSIBLE AND FUNCTIONAL DURING
 ALL PHASES WHEN THE POOL IS OPEN?
  
 WILL THAT EXIT LEAD TO A PUBLIC WAY AT ALL TIMES?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
  
 2B) SHEET LS 0.1 - EXITING OUT AND DOWN STAIR # 5 THERE
 IS AN EGRESS PATH OUT THAT IS GREYED-OUT AND NOT COLOR
 CODED TO ANY PHASE.
  
 THIS EXIT SERVES THE FLOORS ABOVE AND APPEARS TO BE
 UNPORTECTED AND IN A CONSTRUCTION AREA.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT IF
 APPLICABLE.
  
  
  
  
 3) SHEET LS 0.1 - THERE ARE NO INDICATIONS OF ANY
 OVERHEAD PROTECTION IN AREAS THAT MAY HAVING CONTINUING
 CONSTRUCTION OVERHEAD.
  
 PLEASE REVIEW, PROVIDE DETAILS OF NEEDS, ENSURE
 PROTECTION AND CORRECT WHERE APPLICABLE.
  
  
  
 4) SHEET LS 0.1 - THERE ARE INDICATIONS OF CORRIDORS
 BEING BLOCKED OFF WITH TEMPORARY DOORS.
  
 WHAT IS THE CONSTRUCTION MATERIAL TYPE, FIRE RATING AND
 HARDWARE THAT PROVIDES THE APPLICABLE PROTECTION IN
 THESE AREAS?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
 5) REMAINING LIFE SAFETY SHEETS - THERE ARE INDICATIONS
 ON EACH FLOOR OF A WALL CONSTRUCTED WITHIN THE
 CORRIDOR.
  
 WHAT IS THE CONSTRUCTION MATERIAL TYPE AND FIRE RATING
 THAT PROVIDES THE APPLICABLE PROTECTION IN THESE AREAS?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
 6) REMAINING LIFE SAFETY SHEETS - THERE ARE INDICATIONS
 ON EACH FLOOR AT STAIR # 5 OF A TEMPORARY EGRESS DOOR
 UNTIL CONSTRUCTION COMPLETE.
  
 WHAT IS THE CONSTRUCTION MATERIAL TYPE AND FIRE RATING
 THAT PROVIDES THE APPLICABLE PROTECTION IN THESE AREAS?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  