Plan Review Notes For Permit 20061329 |
Permit Number |
20061329 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-17 11:42:11 | THIS PLAN FOR THE PHASED OCCUPANCY IS FAILED BY RICHARD | | GATHRIGHT, ASSISTANT BUILDING OFFICIAL, WITH THE | | FOLLOWING COMMENTS. | | 1. ALL LIFE SAFETY MUST BE IN PLACE, INSPECTED AND | | APPROVED PRIOR TO ANY OCCUPANCY. EXPLAIN HOW YOU WILL | | BE ABLE TO DIVIDE THE PROPOSED OCCUPIED AREA FROM THE | | CONSTRUCTION AREA IN TERMS OF THE SPRINKLER AND ALARM | | SYSTEMS. | | 2. IT APPEARS THAT YOU ARE PROPOSING PHASE 1 OCCUPANCY | | TO BE THE SOUTH WING OF THE BUILDING ALL FLOORS AND THE | | PARKING GARAGE. PHASE 2/3 OCCUPANCY WILL BE THE | | APARTMENTS THAT WRAP AROUND THE GARAGE ALL FLOORS. | | 3. YOU ARE PROPOSING STAIRS 1 AND 5 WILL BE USED BY THE | | APARTMENTS IN THE SOUTH WING OF THE BUILDING. STAIRS 5 | | AND 4 WILL BE USED BY THE PARKING GARAGE | | 4. BY STAIR 4 ON GROUND FLOOR IT APPEARS THAT YOU MAY | | HAVE CREATED A DEAD END BY BLOCKING OFF DOOR | | 5. PROVIDE A NARRATIVE OF YOUR INTENTIONS TO OCCUPY THE | | BUILDING IN PHASES. | | 6. WHERE IS YOUR LEASING OFFICE AND HOW DO YOU PLAN TO | | HAVE THE PUBLIC HAVE ACCESS TO THE LEASING OFFICE? | | WHERE IS THE ACCESSIBLE PARKING FOR THE LEASING OFFICE? | | 7. EGRESS OUT OF THE CONSTRUCTION AREA MUST BE | | MAINTAINED FOR CONSTRUCTION AS WELL AS PROVIDING THE | | REQUIRED EXITING FOR THE APARTMENTS | | | | RICHARD GATHRIGHT | | ASSISTANT BUILDING OFFICIAL | | 5618056679 |
|