Plan Review Notes
Plan Review Notes For Permit 20061271
Permit Number 20061271
Review Stop G
Sequence Number 2
Notes
Date Text
2020-07-22 09:42:532ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20061271
 7/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISED GAS ISOMETRIC DRAWING:
 A) THE DRAWING HAS NOTES INDICATING A 2 PSI DELIVERY
 PRESSURE AT THE METER WITH PIPE SIZING ACCORDING TO
 TABLE 402.4(22) FOR PE AT 2PSI, HOWEVER THE DRAWING
 ALSO HAS NOTES INDICATING 12 " WC REGULATOR AT THE
 METER. FOR CLARIFICATION, PLEASE SHOW THE LOCATION OR
 LOCATIONS OF THE REGULATORS ON THE DRAWINGS. IF THE
 REGULATOR IS AT THE METER THEN PROVIDE THE CORRECT
 SIZING TABLE FOR THE LOW PRESSURE RUNS TO THE
 APPLIANCES- SEE TABLE G2413.4(7) FBC RES OR TABLE
 402.4(21) FBC FUEL GAS. IF THE REGULATORS ARE TO BE
 INSTALLED AT THE APPLIANCES PLEASE SHOW THE LOCATIONS
 ON THE DRAWING.
 B) PROVIDE THE MAKE AND MODEL NUMBERS OF THE REGULATORS
 ON THE DRAWING AND SUBMIT SPECS THAT ARE MARKED UP TO
 INDICATE WHICH MODELS WILL BE INSTALLED AND THEIR
 PRESSURE RANGES.
 C) PLEASE LABEL THE METER AS EITHER NEW OR EXISTING.
 PLEASE NOTE THAT IF THE METER IS EXISTING AND IS
 SUPPLYING OTHER EXISTING GAS FIRED EQUIPMENT AND
 APPLIANCES, IN ORDER TO ENSURE A SAFE OPERATING SYSTEM,
 THE DRAWING MUST BE MODIFIED TO SHOW THE ENTIRE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET AND INCLUDE
 ALL BRANCH PIPE RUNS. EACH NEW AND EXISTING APPLIANCE
 BTUH LOAD SHALL BE INDICATED ON THE DRAWING, AND THE
 TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO
 THE MOST REMOTE OUTLET MUST BE PROVIDED- SECTIONS
 G2413.4.1, G2413.4.2 & G2413.4.3. FOR CLARIFICATION
 PLEASE SHOW THE MAIN PIPE AND TEE LOCATION AT THE METER
 ON THE DRAWING.
  
 2) THE MAIN PERMIT PLANS FOR THE NEW OUTDOOR KITCHEN-
 PERMIT-20020841 DID NOT PROVIDE GAS VENTING PLANS FOR
 THE FIREPLACE AND BBQ GRILL. COMPLETE DRAWINGS AND
 DETAILS ARE REQUIRED. THE NEW SUBMITTAL LABELED AS
 "CHIMNEY SPECS" IS TWO PAGES OF THE ISOKERN GAS LOG SET
 THAT SHOW ONLY THE REQUIRED INPUT GAS PRESSURE AND THE
 BTUH LOAD OF THE UNIT. THE SUBMITTAL FOR THE BBQ IS
 MISSING PAGE 4 OF THE INSTALLATION MANUAL WHICH
 PROVIDES THE EXHAUST HOOD AND EXHAUST DUCT INFORMATION.
 BECAUSE THE UNIT IS BEING INSTALLED UNDER OVERHEAD
 CONSTRUCTION, THE MANUFACTURER REQUIRES A 1200 CFM HOOD
 TO BE INSTALLED. VENTING PLANS SHALL BE DRAWN IN
 ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS-
 SECTIONS G2435.1, G2447.1AND G2427 FBC RES.
  
 A) PLEASE CLARIFY IF YOUR COMPANY IS CONTRACTED TO
 INSTALL THE VENTING- SUBMIT A COPY OF A SIGNED CONTRACT
 INDICATING THE ENTIRE SCOPE OF WORK YOU ARE PROVIDING
 TO THE CUSTOMER. IF THE APPLIANCE VENTING IS NOT IN
 YOUR SCOPE THEN IT MUST BE PERFORMED BY A SEPARATE
 SUB-CONTRACT UNDER PERMIT 20020841. PERMIT 20020841 IS
 STILL AN OPEN PERMIT THAT WOULD HAVE TO BE REVISED TO
 SHOW THE VENTING PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719