2020-07-22 09:42:53 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20061271 |
| 7/20/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REVISED GAS ISOMETRIC DRAWING: |
| A) THE DRAWING HAS NOTES INDICATING A 2 PSI DELIVERY |
| PRESSURE AT THE METER WITH PIPE SIZING ACCORDING TO |
| TABLE 402.4(22) FOR PE AT 2PSI, HOWEVER THE DRAWING |
| ALSO HAS NOTES INDICATING 12 " WC REGULATOR AT THE |
| METER. FOR CLARIFICATION, PLEASE SHOW THE LOCATION OR |
| LOCATIONS OF THE REGULATORS ON THE DRAWINGS. IF THE |
| REGULATOR IS AT THE METER THEN PROVIDE THE CORRECT |
| SIZING TABLE FOR THE LOW PRESSURE RUNS TO THE |
| APPLIANCES- SEE TABLE G2413.4(7) FBC RES OR TABLE |
| 402.4(21) FBC FUEL GAS. IF THE REGULATORS ARE TO BE |
| INSTALLED AT THE APPLIANCES PLEASE SHOW THE LOCATIONS |
| ON THE DRAWING. |
| B) PROVIDE THE MAKE AND MODEL NUMBERS OF THE REGULATORS |
| ON THE DRAWING AND SUBMIT SPECS THAT ARE MARKED UP TO |
| INDICATE WHICH MODELS WILL BE INSTALLED AND THEIR |
| PRESSURE RANGES. |
| C) PLEASE LABEL THE METER AS EITHER NEW OR EXISTING. |
| PLEASE NOTE THAT IF THE METER IS EXISTING AND IS |
| SUPPLYING OTHER EXISTING GAS FIRED EQUIPMENT AND |
| APPLIANCES, IN ORDER TO ENSURE A SAFE OPERATING SYSTEM, |
| THE DRAWING MUST BE MODIFIED TO SHOW THE ENTIRE SYSTEM |
| FROM THE METER TO THE MOST REMOTE OUTLET AND INCLUDE |
| ALL BRANCH PIPE RUNS. EACH NEW AND EXISTING APPLIANCE |
| BTUH LOAD SHALL BE INDICATED ON THE DRAWING, AND THE |
| TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO |
| THE MOST REMOTE OUTLET MUST BE PROVIDED- SECTIONS |
| G2413.4.1, G2413.4.2 & G2413.4.3. FOR CLARIFICATION |
| PLEASE SHOW THE MAIN PIPE AND TEE LOCATION AT THE METER |
| ON THE DRAWING. |
| |
| 2) THE MAIN PERMIT PLANS FOR THE NEW OUTDOOR KITCHEN- |
| PERMIT-20020841 DID NOT PROVIDE GAS VENTING PLANS FOR |
| THE FIREPLACE AND BBQ GRILL. COMPLETE DRAWINGS AND |
| DETAILS ARE REQUIRED. THE NEW SUBMITTAL LABELED AS |
| "CHIMNEY SPECS" IS TWO PAGES OF THE ISOKERN GAS LOG SET |
| THAT SHOW ONLY THE REQUIRED INPUT GAS PRESSURE AND THE |
| BTUH LOAD OF THE UNIT. THE SUBMITTAL FOR THE BBQ IS |
| MISSING PAGE 4 OF THE INSTALLATION MANUAL WHICH |
| PROVIDES THE EXHAUST HOOD AND EXHAUST DUCT INFORMATION. |
| BECAUSE THE UNIT IS BEING INSTALLED UNDER OVERHEAD |
| CONSTRUCTION, THE MANUFACTURER REQUIRES A 1200 CFM HOOD |
| TO BE INSTALLED. VENTING PLANS SHALL BE DRAWN IN |
| ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS- |
| SECTIONS G2435.1, G2447.1AND G2427 FBC RES. |
| |
| A) PLEASE CLARIFY IF YOUR COMPANY IS CONTRACTED TO |
| INSTALL THE VENTING- SUBMIT A COPY OF A SIGNED CONTRACT |
| INDICATING THE ENTIRE SCOPE OF WORK YOU ARE PROVIDING |
| TO THE CUSTOMER. IF THE APPLIANCE VENTING IS NOT IN |
| YOUR SCOPE THEN IT MUST BE PERFORMED BY A SEPARATE |
| SUB-CONTRACT UNDER PERMIT 20020841. PERMIT 20020841 IS |
| STILL AN OPEN PERMIT THAT WOULD HAVE TO BE REVISED TO |
| SHOW THE VENTING PLANS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |