2020-07-13 16:26:29 | PLAN REVIEW ? FUEL GAS - GENERATOR |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| |
| 1) GAS ISOMETRIC DRAWING: |
| A) THE DRAWING IS INCOMPLETE AND MUST BE MODIFIED TO |
| SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH PIPES FROM |
| THE METER TO THE MOST REMOTE OUTLET. THE BTUH LOAD OF |
| EACH APPLIANCE AND THE LOCATIONS OF REGULATORS SHALL BE |
| INDICATED ON THE DRAWING- SECTIONS G2412.3 & G2412.4 |
| FBC RES. |
| B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| G2413.4.3. |
| B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE |
| OUTLET OF THE REGULATOR- SECTION G2421.1 |
| C) CORRECT THE BTUH LOAD OF THE GENERATOR. THE |
| SUBMITTED SPECS INDICATE 306.000 BTUH FULL LOAD- |
| G2413.2 FBC RES. |
| 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH |
| MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET |
| AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION |
| G2421.1. |
| |
| |