Plan Review Notes For Permit 20061224 |
Permit Number |
20061224 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-08-11 14:43:55 | 08/11/20 2ND PLUMBING/POOL REVIEW**DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. SECOND REQUEST PROVIDE MANUFACTURER'S SPECIFICATION | | / INSTALLATION MANUAL FOR ALL POOL EQUIPMENT; PROVIDE | | INLINE EQUIPMENT SPECS IN THE PIPING SYSTEM ( I.E., | | FILTER, PUMP, ETC. NEED TO PROVIDE HEAD LOSS TO SHOW | | WHERE ENGINEER GOT CALCS FOR TDH) PER THE WPB FBC | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|