Plan Review Notes
Plan Review Notes For Permit 20061214
Permit Number 20061214
Review Stop B
Sequence Number 2
Notes
Date Text
2021-01-12 07:21:34PLAN REVIEW / BUILDING
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE INCREASED FASTENER DENSITIES PER ENHANCED
 UPLIFT PRESSURES OF RERIMETER AND CORNERS PER NOA
 18-0919.12 LIMITATION # 7. CALCULATIONS SHALL BE SIGNED
 AND SEALED BY A DESIGN PROFESSIONAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. REMOVE PRODUCT APPROVALS AND NOA'S OF WINDOWS AND
 DOORS. ALSO REMOVE FLOOR PLAN FOR WINDOW AND DOOR
 INSTALLATION.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.