Plan Review Notes
Plan Review Notes For Permit 20061197
Permit Number 20061197
Review Stop B
Sequence Number 2
Notes
Date Text
2020-07-06 08:18:51ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) -
 SEE NOTE NUMBER 9 ON THE PRODUCT APPROVAL. SIGNED AND
 SEALED DRAWINGS OR DOCUMENTS WILL NEED TO BE DIGITALLY
 SIGNED AND SEALED TO BE USED IN ELECTRONIC PLAN REVIEW.
 SHOW THE WIND DESIGN DATA USED PER 2017 FBC AND ASCE
 7-10 - WIND SPEED - EXPOSURE - RISK CATEGORY - ETC.
  
 FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL
 SIGNATURE
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY.
  