Plan Review Notes For Permit 20061197 |
Permit Number |
20061197 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-07-06 08:18:51 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) - | | SEE NOTE NUMBER 9 ON THE PRODUCT APPROVAL. SIGNED AND | | SEALED DRAWINGS OR DOCUMENTS WILL NEED TO BE DIGITALLY | | SIGNED AND SEALED TO BE USED IN ELECTRONIC PLAN REVIEW. | | SHOW THE WIND DESIGN DATA USED PER 2017 FBC AND ASCE | | 7-10 - WIND SPEED - EXPOSURE - RISK CATEGORY - ETC. | | | | FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL | | SIGNATURE | | 668.003(2) AND (3), F.S. | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE | | THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | AUTHORITY. | | |
|