Plan Review Notes For Permit 20061197 |
Permit Number |
20061197 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-29 11:08:01 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | APPROVAL HAS A MAXIMUN DESIGN PRESSURE OF (-45) ROOF | | WIND ZONES 2 AND 3 REQUIRE A HIGHER PRESSURE THAN THE | | MAXIMUM SHOWN ON THE PRODUCT APPROVAL. | | |
|