2020-07-14 09:11:46PLAN REVIEW ? BUILDING - GENERATOR
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 2) STRUCTURAL DETAIL SHALL BE SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL.
  