Plan Review Notes
Plan Review Notes For Permit 20061112
Permit Number 20061112
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-16 15:21:531ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20061112
 7/16/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1 & P-2: INDICATE THE DISTANCE FROM THE NEW
 SHOWER DRAIN TRAPS TO THE EXISTING VENTS DOES NOT
 EXCEED 8' PER SECTION AND TABLE P3105.1 FBC RES.
 OTHERWISE PROVIDE INDIVIDUAL VENTS.
  
 2) P-1 & P-2: INDICATE HOW THE SUPPLY LINES TO THE
 DISHWASHER AND ICE MAKER WILL PROTECTED AGAINST
 BACKFLOW- SECTIONS P2717.1 & P2902.1 FBC RES.
  
 3) PROVIDE SHOWER PAN DETAILS FOR THE NEW MASTER AND
 BEDROOM BATHS- SECTIONS P2709.1 & P2709.2
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS- SECTION P2801.3.
  
 5) THE NEW MASTER BATH TUB FAUCET SHALL BE IN
 COMPLIANCE WITH SECTIONS P2713.3 & P2902.4.2 . PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TUB VALVE
 AND THE NEW SHOWER VALVES- SECTION P2708.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  