Notes
Date Text
2020-07-22 10:21:09ADDITION AND REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS,
 OVERHEAD GARAGE DOOR ETC.
 2) ON THE DRAWINGS SHOW THAT THE GENERATOR IS TO BE ON
 A SEPARATE PERMIT.
 3) PLEASE CIRCLE THE ROOF TILE ATTACHMENT TO BE USED ON
 THE PROVIDED TILE PRODUCT APPROVAL - IF USING ADHESIVE
 PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVAL FOR THE ADHESIVE.
  
  