Plan Review Notes
Plan Review Notes For Permit 20061041
Permit Number 20061041
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-27 10:37:23PLAN REVIEW ? GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
  