2020-07-23 10:54:47 | PLAN REVIEW BUILDING |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PRE-CAST SLAB DETAIL REQUIRES VALID DIGITAL |
| SIGNATURE AND SEAL OF DESIGN PROFESSIONAL. |
| |
| DIGITAL REVIEW |
| |
| 1A. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH |
| FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE |
| NEXT REVIEW CYCLE REQUIRE REVIEW. |
| |
| 1B.. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. |
| |
| 1C. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY |
| DIGITAL SIGATURES AND SEALS PER FS 668.003. |
| |
| 2. PROVIDE WIND LOAD DESIGN PRESSURE CALCULATIONS PER |
| PRE-CAST SLAB DETAIL. |
| |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). |
| |