Plan Review Notes For Permit 20061029 |
Permit Number |
20061029 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-27 15:25:24 | PLAN REVIEW ? GENERATOR - ? FUEL GAS | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | CITY RECORDS INDICATE AN EXISTING GAS SERVICE AT THIS | | RESIDENCE. | | | | 1) GAS ISOMETRIC DRAWING: | | | | 1A) PROVIDE DETAIL OF GAS DEVICES AT GENERATOR. INCLUDE | | S/O VALVE, DRIP LEG AND REGULATOR. | | 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE | | OUTLET OF THE REGULATOR- SECTION G2421.1 | | 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC | | RES. | | | | 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH | | MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET | | AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION | | G2421.1. | | |
|