Plan Review Notes
Plan Review Notes For Permit 20061029
Permit Number 20061029
Review Stop G
Sequence Number 1
Notes
Date Text
2020-07-27 15:25:24PLAN REVIEW ? GENERATOR - ? FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CITY RECORDS INDICATE AN EXISTING GAS SERVICE AT THIS
 RESIDENCE.
  
 1) GAS ISOMETRIC DRAWING:
  
 1A) PROVIDE DETAIL OF GAS DEVICES AT GENERATOR. INCLUDE
 S/O VALVE, DRIP LEG AND REGULATOR.
 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC
 RES.
  
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1.
  