2020-10-20 07:08:41 | PLAN REVIEW GENERATOR - FUEL GAS |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| CITY RECORDS INDICATE AN EXISTING GAS SERVICE AT THIS |
| RESIDENCE. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| PREVIOUS COMMENTS. |
| |
| |
| 1) GAS ISOMETRIC DRAWING: |
| 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM |
| INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST |
| REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE |
| AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON |
| THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. (NOT |
| ADDRESSED) (PROVIDE TOTAL LOAD OF EXISTING APPLIANCES - |
| W/H, DRYER, RANGE AND FUTURE BBQ GRILL) |
| |
| NOTE: YOU MAY PROVIDE THE EXISTING LOAD AS ONE |
| CALCULATION ON THE GAS RISER |
| |
| 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| G2413.4.3. (NOT ADDRESSED) |
| |
| 1B) CORRECTED |
| 1C) CORRECTED |
| |
| |
| |