Plan Review Notes
Plan Review Notes For Permit 20060986
Permit Number 20060986
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-13 15:51:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) MAINS NOT GROUPED PER 230.72
  
 230.72 GROUPING OF DISCONNECTS (A) GENERAL. THE TWO TO
 SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE
 GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE
 THE LOAD SERVED.
  