Plan Review Notes
Plan Review Notes For Permit 20060970
Permit Number 20060970
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-14 08:40:17FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NO ADDED VALUE FOR THE ADDITIONAL WORK SHOWN ON PLANS.
  
 NO LOW VOLTAGE SHOWN ON PLANS SEPARATE PERMIT IS
 REQUIRED FOR LOW VOLTAGE WORK. (ONE TV OUTLET SHOWN)
  
 PANTRY REQUIRES OUTLETS PER 210.52(C)(1)
  
 210.52 (C) COUNTERTOPS. IN KITCHENS, PANTRIES,
 BREAKFAST ROOMS, DINING ROOMS, AND SIMILAR AREAS OF
 DWELLING UNITS, RECEPTAC LE OUTLETS FOR COUNTERTOP
 SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(C)(1) THROUGH (C)(5). (1) WALL COUNTERTOP
 SPACES. A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 WALL COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.
  