Plan Review Notes For Permit 20060970 |
Permit Number |
20060970 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-14 08:40:17 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | NO ADDED VALUE FOR THE ADDITIONAL WORK SHOWN ON PLANS. | | | | NO LOW VOLTAGE SHOWN ON PLANS SEPARATE PERMIT IS | | REQUIRED FOR LOW VOLTAGE WORK. (ONE TV OUTLET SHOWN) | | | | PANTRY REQUIRES OUTLETS PER 210.52(C)(1) | | | | 210.52 (C) COUNTERTOPS. IN KITCHENS, PANTRIES, | | BREAKFAST ROOMS, DINING ROOMS, AND SIMILAR AREAS OF | | DWELLING UNITS, RECEPTAC LE OUTLETS FOR COUNTERTOP | | SPACES SHALL BE INSTALLED IN ACCORDANCE WITH | | 210.52(C)(1) THROUGH (C)(5). (1) WALL COUNTERTOP | | SPACES. A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH | | WALL COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. | | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT | | ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.) | | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT | | SPACE. | | |
|