Plan Review Notes For Permit 20060968 |
Permit Number |
20060968 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-08 13:27:46 | POOL BARRIER | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) A CONVENTIONAL SHADOW BOX FENCE DOES NOT COMPLY WITH | | THE FBC BARRIER REQUIREMENTS ( THE VERTICAL MEMBERS ON | | THE NEIGHBORS SIDE CANNOT HAVE A SPACE BETWEEN THEM OF | | MORE THAN 1 3/4" - YOU WOULD NEED TO ADD AN EXTRA | | VERTICAL MEMBER TO HAVE NO SPACE OR A SPACE LESS THAN 1 | | 3/4") PER FBC R4501.17.1.4 | | WHERE THE BARRIER IS COMPOSED OF HORIZONTAL AND | | VERTICAL MEMBERS AND THE DISTANCE BETWEEN THE TOPS OF | | THE HORIZONTAL MEMBERS IS LESS THAN 45 INCHES (1143 | | MM), THE HORIZONTAL MEMBERS SHALL BE LOCATED ON THE | | SWIMMING POOL SIDE OF THE FENCE. SPACING BETWEEN | | VERTICAL MEMBERS SHALL NOT EXCEED 1 3/4 INCHES (44 MM) | | IN WIDTH. WHERE THERE ARE DECORATIVE CUTOUTS WITHIN | | VERTICAL MEMBERS, SPACING WITHIN THE CUTOUTS SHALL NOT | | EXCEED 13/4 INCHES (44 MM) IN WIDTH. | | |
|