Plan Review Notes
Plan Review Notes For Permit 20060955
Permit Number 20060955
Review Stop G
Sequence Number 3
Notes
Date Text
2020-09-28 08:46:593RD REVIEW FBC-2017 RES.
 PERMIT- 20060955
 9/25/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS PROM THE PREVIOUS REVIEWS HAVE NOT BEEN
 ADDRESSED.
  
 1) REVISE THE RISER TO SHOW THE COMPLETE PIPING SYSTEM
 INCLUDING PIPE RUNS TO ALL NEW AND EXISTING APPLIANCES
 AND EQUIPMENT, AND SHOW THE CORRECT TOTAL AND
 INDIVIDUAL LOADS OF THE SYSTEM- SECTIONS G2412.3,
 G2412.4, & G2413.2 FBC RES. INCLUDE THE TOTAL LENGTH OF
 THE INTERIOR PIPING RUN AND THE TOTAL DEVELOPED LENGTH
 OF THE ENTIRE SYSTEM- SECTIONS G2413.4.1 AND G2413.4.2
 FBC RES. THE DRAWING SHALL INDICATE THE TYPE AND SIZE
 OF MAIN SUPPLY PIPE FROM THE METER TO THE TEE. PER CITY
 RECORDS AT A MINIMUM THERE IS AN EXISTING GAS WATER
 HEATER BUT ALL CONNECTED EXISTING HAPPLIANCES AVE TO BE
 ACCOUNTED FOR WHETHER LEGALLY PERMITTED OR NOT- SECTION
 107.2.1 WPB.
  
 A) THE SUBMITTED SPECS FOR THE KOHLER 20 KW INDICATE A
 FULL LOAD CAPACITY OF 340,000 BTUH AND AN INPUT
 PRESSURE AT 3.5-11 IN. W.C. PLEASE CORRECT THE LOAD ON
 THE DRAWING.
  
 B) AS PREVIOUSLY REQUESTED SHOW THE LOCATION OF THE
 REGULATOR AT THE GENERATOR, AND INDICATE THE MAKE AND
 MODEL. SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE; SHOW THE SHUTOFF VALVE, AND THE DRIP LEG-
 SECTIONS 2420.5, 2421.2, 2421.2(7), AND 2419.2 FBC RES.
 PLEASE SUBMIT MARKED UP OR HIGHLIGHTED SPECS FOR THE
 REGULATOR TO SHOW IT IS SUITABLE FOR OUTDOOR USE,
 INDICATE THE SELECTED MODEL, INLET AND OUTLET
 PRESSURES, AND ORIFICE SIZE.
  
 E) PIPE SIZING FOR THE SYSTEM SHALL BE IN ACCORDANCE
 WITH SECTION G2413.3 FBC RES. PLEASE SEE TABLES
 G2413.4(1)- G2413.4(8) AND LIST THE PIPE SIZING TABLE
 FOR EACH TYPE OF PIPING IN THE SYSTEM. TYPICALLY TABLE
 G2413.4(1) [402.4(2)] IS USED FOR LOW PRESSURE SCHED.
 40 METALLIC PIPE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  