Plan Review Notes For Permit 20060955 |
Permit Number |
20060955 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-02 12:59:13 | 1ST REVIEW FBC-2017 RES. | | PERMIT- 20060995 | | 7/2/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SIGNATURE OF THE FL. LICENSED GAS CONTRACTOR SHALL | | BE ON THE GAS PIPING LAYOUT DRAWING- SECTION 107.2.1 | | WPB, AND FL. STATUTES 471 & 489. | | | | 2) INDICATE THE PRESSURE AT THE METER AND SHOW THE | | LOCATION AND TYPE OF NEW SET DOWN REGULATOR TO BE | | INSTALLED IF REQUIRED- SECTION G2421 FBC RES. | | | | 3) SUBMIT MANUFACTURER?S DATA SHEETS FOR THE GENERATOR, | | REGULATOR, AND QUICK CONNECT FLEX LINE- SECTION 107.2.1 | | WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH | | |
|