Plan Review Notes For Permit 20060954 |
Permit Number |
20060954 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-07-08 08:56:27 | | | PLAN | | REVIEW COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN | | ADDRESSED. | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) I AM NOT ABLE TO REVIEW DUE TO THE MISSING AND | | INACCURATE INFORMATION THAT HAS BEEN PROVIDED. THE | | INSTALLATION SCHEDULE IS INCORRECT AND MISSING | | INFORMATION. THE OPENING SIZE IS TO BE THE WIDTH AND | | HEIGHT OF THE OPENING IN INCHES. THE SHUTTER SPANS ARE | | NOT PROVIDED. FBC 107 | | | | 2) HI LIGHT OR CIRCLE THE ITEMS THAT APPLY TO THIS | | PROJECT IN THE PRODUCT APPROVAL FOR THE STORM PANELS. | | SPECIFY THE MOUNT TYPE SECTIONS THAT WILL BE USED FOR | | EACH OF THE OPENINGS, THEY HAVE CAPITAL LETTERS IN | | FRONT OF THEM IN THE PRODUCT APPROVAL DRAWINGS. THIS IS | | NOT THE SAME AS THE CONNECTION TYPES (SUCH AS C1 OR | | C2). FBC 107 | | | | 3) HI LIGHT OR CIRCLE THE APPROPRIATE ITEMS IN THE | | ANCHOR SPACING TABLES. MARK THE ANCHOR, THE DESIGN | | PRESSURE, THE SPAN, THE SPACING, ETC ON THE PROPER | | TABLE. FBC 107 |
|